INSTALLATION & WIRING
VCB-X Controller Field Technical Guide
24
Duct Mounted E-BUS CO
2
Sensor
The OE256-07 Duct Mounted E-BUS CO
2
Sensor with Remote
Pickup Tube is used for sensing the current CO
2
level in the HVAC
unit’s return air stream. This is useful when you want an average
CO
2
reading in the area served by the HVAC unit or when you don’t
want a wall mounted E-BUS CO
2
Sensor due to sensor tampering
concerns in the space.
The OE256-07 Duct Mounted Return Air CO
2
Sensor is comprised
of the CO
2
Sensor, the WattMaster Aspiration Box Assembly, and a
Remote Pickup Tube.
The Duct Mounted Return Air E-BUS CO
2
Sensor with Remote
Pickup Tube is designed to be mounted in the return air duct of the
HVAC unit and uses its integral aspiration box to sample the CO
2
level in the duct. See
Figure 10
below for wiring and installation
details.
NOTE:
If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
Figure 10: OE256-07 - Duct Mounted E-BUS CO
2
Sensor Wiring
Duct Mounted E-BUS CO
2
Sensor
OE256-07 Duct Mounted
E-BUS CO Sensor
2
Note:
1.)
The Duct Mounted E-BUS CO Sensor
Connects To The
Controller Using An
EBC E-BUS Cable Of The Required Length
Or The Provided 10 Foot EBC Cable.
2
VCB-X
VCB-X Controller
MADE IN USA
10 Foot EBC
E-BUS Cable
(Provided)
EBC E-BUS
Cable
with Jack
Connection
37X04
1.2
1.6
<PC>
4 3 2 1
3M
X
ENTER
UP
DOWN
ALARM
CANCEL
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMM
LOOP. WIRE
“R” TO “R”,
“T” TO “T”
“SHLD” TO “SHLD”
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
www.aaon.com
www.orioncontrols.com
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
AAON : V28940
AAON Coil: J00142
ANALOG INPUTS
AI1
= SPC (SPACE TEMP SENSOR)
AI2
AI3
AI4
AI5
BI1
BI2
BI3
BI4
AO1
AO2
AO3
TR1
= SAT (SUPPLY AIR TEMP SENSOR)
= OAT (OUTDOOR AIR TEMP SENSOR)
= DCT (DIGITAL COMP DISCH TEMP SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET
= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER
= COIL TEMP SWITCH
= FAN VFD
= ECONOMIZER
= MOD HEATING
= DIGITAL COMP
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
BINARY INPUTS
G OUTPUTS
TRIAC OUTPUT
ANALO
WattMaster Label
#SW000061
Rev.: 1A
E-BUS
EXPANSION
E-BUS
EXPANSION
+24
VAC
GN
D
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY
COMMON
LT
17
8
5
485 DRV
BACNET
U2
TB7
R68
T-
SH
R+
3650
.1uF
C81
Revised 4/30/12
Содержание OE335-26B-VCBX-A
Страница 115: ...NOTES VCB X Controller Field Technical Guide 115...