User manual
FLEXI 50
18
8.2
Description of the button on the remote control
ON/Standby. The Standby mode depends on the position of the DIP
switch 2 (see section Setting the ventilator operation mode using DIP
switches). The same button is used to reset alarms (Alarm) and to turn
off the timers.
Ventilator speed selection: Speed III-II-I respectively.
Regeneration mode
The rotation direction of both fans changes to opposite every 70
seconds. Heat recovery is performed in this mode. The fan rotation
direction depends on the position of the DIP switch 3.
Ventilation mode
The ventilator operates in the supply or extraction mode at a set speed.
The fan rotation direction depends on the position of the DIP switch 3.
Timer control buttons:
Party mode: the timer activates operation of the unit at
Speed Ill for a set time period, 4 hours by default. The timer
setting may be changed during setup of the unit on the mobile
device .
Night mode: the timer activates operation of the
ventilation unit at Speed I for a set time period, 8 hours by
default. The timer setting may be changed during setup of the
unit on the mobile device.
The ventilation unit reverts to operation with a previous speed setting
upon elapse of the set time period. Press any speed setting key to
deactivate the timer or press the timer control button once again.