16
7.3
Setting the ventilator operation mode using DIP switches
Prior to operating the ventilator set it up using the DIP
switch. It is located on the controller circuit board.
To access the DIP switch, take off the front panel of the
indoor unit and uplift the rubber plug that covers the
switch.
Setting the role of the ventilator in the network
ON - slave unit (hereinafter referred to as "Slave unit")
OFF - master unit (hereinafter referred to as "Master unit")
Standby mode setup
Min - the ventilator operates at Speed I in the Standby mode.
OFF - the ventilator is switched off in the Standby mode.
Settino of the fan rotation direction*
ON –
•
in the Ventilation mode the ventilator supplies the air to the room.
•
in Regeneration mode the ventilator starts operating first in supply mode.
OFF –
•
in the Ventilation mode the ventilator extracts the air from the room.
•
in Regeneration mode the ventilator starts operating first in extract mode.
Restore factory default settings
ON –
restore factory default settings. For this purpose, move the switch on the operating
ventilator to the ON position, after the sound signal
turn the switch to the OFF position.
OFF – standard operation of the unit.
*To form an optimal ventilation mode in the room, it is recommended to use either one or an even number of networked ventilators.
The setting is carried out in such a way that during each operation interval one half of the ventilators supplies air to the room, and the
other half extracts air out of the room.