■ GSC-02A
User's Manual
■
6. GSC-02A Setting
Initialize your GSC-02A to match to the target stages and host environment (your PC, etc.). The
initialization includes DIP Switch settings and current adjustments (RUN/STOP) for each axis
motor.
6-1. Set parameters with DIP Switch
Initialize your GSC-02A by setting each switch to ON/OFF as follows:
Parameter Assignment in the DIP Switch:
Table6-1-1: DIP switch setting items
DIP Switch No.
Items
Parameters
1,2
Baud rate
2400 / 4800 / 9600 / 19200
3
Detecting the mechanical origin
MARK method / MINI method
4
Input logic for the limit sensor
Normal open/ Normal close
5
Specify whether to return mechanical origin
for each axis
First axis only/ Both axis
Switch settings and Corresponding Parameters (Set to ON by turning to the downside)
Table6-1-2: DIP switch setting list
Items
Dip Switch No.
Descriptions
Baud rate
SW No.1
SW No.2
ON
ON
2400 [bps]
OFF
ON
4800 [bps]
ON
OFF
9600 [bps]
OFF
OFF
19200 [bps]
Detecting the
mechanical origin
SW No.3
ON
MARK method*
OFF
MINI method*
Input logic for the
limit sensor
SW No.4
ON
Normal open
OFF
Normal close
Specify whether to
return mechanical
origin for each axis
SW No.5
ON
First axis only
OFF
Both axis
Note) Shaded areas in the list show our factory settings. Tale care to handle the very small DIP
Switch so as to avoid giving damage to them during the settings. Use appropriate tools
such as sharp tweezers for setting switches on the DIP Switch. For our OSMS series
stages, select MINI method and Normal close.
*) For details on the method of return to origin, see page 20.