Fire Protection  |  Data sheet No. 41350  |  Version 01-2019  | 

9

 | 

10

KRM-X® Duct Smoke Detector

Maintenance and repair

1. Instructions for Operation and 

Maintenance

The operator is responsible for the safe function of the ven-
tilation system. He has to ensure that the smoke detectors 
are always operational and properly maintained, including all 
controlling components and systems.

The smoke detector must be tested at least once a year in order 
to ensure that it performs reliably over long time periods. With-
out maintenance the sensor will become soiled sooner or later, 
depending on environmental conditions, and will eventually 
trigger an alarm, i.e. a false alarm.

All types will give a specific “maintenance due”
signal at a contamination level of 70 % (display flashes, 
contamination relay drops out).

The smoke detector is equipped with a 2-digit digital contam-
ination indicator, allowing maintenance according to demand. 
The smoke detector must be replaced at a contamination level 
70 % or higher. The contact provided for this “contamination” 
signal should be connected to the automation station.

2. Maintenance and repair work

Before starting maintenance work, it must be clarified with the 
staff whether the unit needs to remain responsive to smoke 
while work is in progress. If a brief shutdown cannot be cannot 
be tolerated for operational reasons, measures must be taken 
to prevent a shutdown. If necessary, a bridge can be placed 
over the alarm contact for this purpose. After completion of 
maintenance work, any such bridge must be removed, and a 
complete functional test of all system components must be 
carried out. Any defects found must be rectified immediately. 
Every maintenance check must be documented in a report, and 
the results must be entered in the operation manual and signed 
by the operator in charge.

Caution:

Before opening the housing, disconnect all supply voltages. The 
housing may only be opened by a qualified electrician. Supply 
and switching voltage ratings must be observed

Please observe the following symbols on the device:

The following work is required and can only be carried out by us 
or by our authorized technicians: 

1. The smoke detector can be accessed by removing the cover.

2. The detector can be removed by turning it on the base by 

about 20° to the left. The detector must be replaced by a new 
detector if it has reached the contamination limit (indicator 
>70 %) or if the prescribed standard replacement period has 
expired, whichever is earlier.

3. The following must also be cleaned:

• 

the cover

• 

the TurboTube measuring tube

• 

the inner housing

Caution – voltage

Turn voltage off before working on equipment.

Please follow the instructions.

Содержание KRM-X

Страница 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Страница 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Страница 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Страница 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Страница 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Страница 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Страница 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Страница 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Страница 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Страница 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...

Отзывы: