7. Check with the operator about the function of downstream 

systems and components, such as:

• 

Turning off of fans

• 

Closing of flaps

• 

Notification to the building automation system

• 

When checking network failure and recovery, does the 
detector return to its normal function and does it unlock 
again from the ”smoke alarm” state and return to its normal 
function when the alarm has been reset? Does the detector 
return to the alarm state and lock up if the smoke alarm 
persists? 

• 

The detector can be released by pressing the reset button 
or briefly disconnecting the voltage. 

• 

Release and approve for operation.

Dimensions

Dimensions in mm

4. Check the electrical connections, tightening the terminals as 

necessary. Make a visual inspection of and clean the electrical 
circuit board as well as the inner housing as necessary. Check 
all gaskets.

5. Assemble all components, observing the specified torque  

of 1.2 Nm for screws.

6. Perform a functional test by triggering the smoke detector 

with Oppermann test spray. 

Содержание KRM-X

Страница 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Страница 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Страница 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Страница 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Страница 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Страница 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Страница 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Страница 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Страница 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Страница 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...

Отзывы: