Fire Protection  |  Data sheet No. 41350  |  Version 01-2019  | 

7

 | 

10

KRM-X® Duct Smoke Detector

Installation

1.

 

Drill a hole 43 – 44 mm in diameter at the intended  

mounting location.

Note: The TurboTube measuring tube can be installed on top or  

at the bottom or side of the duct for all duct cross-sections  

(including round ducts).

2. 

• 

Determine how long the measuring tube must be.

• 

If necessary, shorten the tube; minimum length 160 mm including  
end plug (cutting length 145 minimum – see drawing).

• 

Deburr the cutting face and put the end plug back on 

up to the stop 

collar

Note: The KRM-X must only be used with the red end plug.  

Observe the mark on the end plug indicating the flow direction. 

3.

• 

Determine the direction of flow and mount the adapter plate such 
that the line on the adapter plate under the text ”Strömungsrichtung” 
is parallel to the flow direction.

• 

Four self-tapping screws (not included in delivery) serve for attaching 
the adapter plate to the sheet metal duct.

4.

 

Installation on the duct

• 

Rectangular air duct – see picture on the right

• 

For installation on a circular air duct, use the KS-X-type mounting 
bracket and the rubber bushing. The mounting bracket has bend 
perforations for adaption to a round duct.

The KS-X-type mounting 
bracket is supplied flat.

5. 

Installation on air ducts with insulation

• 

Use the rubber bushing and insert it into the ø 43 – 44 mm opening 
 in the air duct.

• 

Install the mounting bracket.

• 

Insert the assembled adapter plate together with the measuring tube 
by sliding the measuring tube through the bushing, and screw the 
adapter plate onto the mounting bracket using 4 self-tapping screws. 
Then the insulation can be installed.

min. 145 mm

Mounting 

bracket

inside

 Rubber bushing

Mounting 

bracket

Insulation

outside

Caution: operation without 
end plug not allowed

Cutting length of aluminum tube 145 

Minimum length 160   

Содержание KRM-X

Страница 1: ...S485 MOD BAC only Accessories Mounting bracket KS X for insulated circular ducts KS X for insulated circular ducts in combination with WDG X Housing WDG X protective insulating housing with alarm disp...

Страница 2: ...nected Note The floating switching contacts terminals 11 17 should be assigned as uniformly as possible to an installation category according to EN 60730 1 These switching contacts are to be used for...

Страница 3: ...ng segment display 00 99 Contamination in Flashes starting at 70 contamination relay drops out at 99 the alarm LED alarm lights up Failure E g smoke detector missing communication with smoke detector...

Страница 4: ...when airflow is too low and air relay only present on DIBt versions drops out Check smoke detector position in the duct check sampling tube TurboTube for contamination and clean if necessary Programm...

Страница 5: ...unting bracket this makes it possible to mon itor ducts up to 100 mm There is no maximum width height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube...

Страница 6: ...structurally possible If the positioning recommendations cannot be followed for structural reasons the KRM X should be mounted such that reliable smoke detection and airflow are nonetheless ensured T...

Страница 7: ...lel to the flow direction Four self tapping screws not included in delivery serve for attaching the adapter plate to the sheet metal duct 4 Installation on the duct Rectangular air duct see picture on...

Страница 8: ...The green LED 12 lights up Press the alarm reset button 9 to perform a simple initial functional test All LEDs must light up and all relays drop out The units con nected to the relays are activated T...

Страница 9: ...ive to smoke while work is in progress If a brief shutdown cannot be cannot be tolerated for operational reasons measures must be taken to prevent a shutdown If necessary a bridge can be placed over t...

Страница 10: ...eturn to its normal function and does it unlock again from the smoke alarm state and return to its normal function when the alarm has been reset Does the detector return to the alarm state and lock up...