background image

 1 

E56-6001-000 

  

02/16/2018

SPECIFICATIONS

Electrical Characteristics

External Supply Voltage 

18 – 30 VDC

Remote Reset Time 

 External monitor must be pulled low for a 
minimum of 100 msec

Power Reset 

1 sec

Average Operating Current 

Fan High – 465mA, 11.2W

 

Fan Med – 340mA, 8.2W

 

Fan Low – 220mA, 5.3W

Alarm Current 

Fan High – 493mA, 11.85W

 

Fan Med – 368mA, 8.85W

 

Fan Low – 248mA, 6W

Relay Contact Ratings 

3.0A @ 30VDC, 0.5A @125VAC

Environmental Ratings

Operating Temperature 

-10°C to 55°C 

Sampled Air Temperature 

-20°C to 160°C

Humidity 

10 to 95% non-condensing

IP Rating 

IP30

Coverage Area 

 Up to 4,800 sq.m (subject to local standards 
and requirements) 

Air Movement 

0 – 1,219.2 m/min

9400XE FAAST 

Fire Alarm Aspiration Sensing Technology

®

COMPREHENSIVE USER GUIDE

INTRODUCTION

SCOPE OF THIS MANUAL ..................................................................................... 2

DESCRIPTION

ITEMS INCLUDED WITH UNIT .............................................................................. 2

Connecting to FAAST XT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Connecting to FAAST via USB  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

CONFIGURE YOUR PC .......................................................................................... 2

CONNECT USING PIPEIQ ..................................................................................... 2

INSTALLATION

PIPE INSTALLATION .............................................................................................. 3

PHYSICAL UNIT INSTALLATION ............................................................................ 3

SECURING THE MOUNTING BRACKET ................................................................ 3

MOUNTING THE DETECTOR TO THE BRACKET .................................................. 3

Connecting the Air Sampling Pipe   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

EXHAUST PIPE ...................................................................................................... 3

WIRING ................................................................................................................. 4

POWER CABLES ................................................................................................... 4

CONDUIT USAGE .................................................................................................. 4

SYSTEM WIRING ................................................................................................... 4

SYSTEM POWERING ............................................................................................. 5

USER INTERFACE

PARTICULATE LEVEL DISPLAY ............................................................................. 5

ALARM LEVEL DISPLAY ........................................................................................ 6

AIR FLOW DISPLAY ............................................................................................... 6

FAULT DISPLAY ..................................................................................................... 6

LCD USER INTERFACE ......................................................................................... 7

HOME SCREEN ..................................................................................................... 7

MAIN MENU SCREEN  ......................................................................................... 8

Active Faults  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Air Flow  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Functions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

CONFIGURATION

GENERAL SETTINGS ............................................................................................ 8

Network   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Email Menu   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Modbus   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Alarm Settings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Event History   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Message Log   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

LCD Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Display Time Out   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

DIAGNOSTIC.......................................................................................................... 9

MODES OF OPERATION

INITIALIZATION ...................................................................................................... 9

CONFIGURATION OVERVIEW................................................................................ 9

FAN SPEED CONFIGURATION .............................................................................. 9

ALARM AND RELAY CONFIGURATION ............................................................... 10

AUDIBLE INDICATOR CONFIGURATION ............................................................. 10

FAILURE OF CONFIGURATION VALIDATION ....................................................... 10

POWER GLITCH DURING CONFIGURATION ....................................................... 10

NORMAL ............................................................................................................. 10

TEST .................................................................................................................... 10

SOUNDER TEST .................................................................................................. 10

RESET ................................................................................................................. 10

RESET AIRFLOW BASELINES ............................................................................. 10

ISOLATION ........................................................................................................... 10

DISABLE MODE .................................................................................................. 10

ACCLIMATE® MODE ........................................................................................... 10

SETTING ACCLIMATE MODE .............................................................................. 11

DAY, NIGHT AND WEEKEND MODE ................................................................... 11

LOGS

EVENT LOG ......................................................................................................... 11

DATA TREND LOG ............................................................................................... 11

MESSAGE LOG ................................................................................................... 11

MISCELLANEOUS

EXTERNAL MONITOR/RESET ............................................................................. 11

ETHERNET CONNECTION .................................................................................. 11

USB CONNECTION ............................................................................................. 11

PIPE NETWORK .................................................................................................. 11

WEB SERVER ...................................................................................................... 11

EMAIL NOTIFICATION ......................................................................................... 11

CANNED SMOKE TESTING ................................................................................ 11

MAINTENANCE  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11

TABLE OF CONTENTS

E56-600

1-000

Exterior Dimensions

Height 

338 mm

Width 

333 mm

Depth 

191 mm

Cable Access 

 25.4 mm cable access holes on top, bottom 
and back of unit

Wire Gauge 

12 Ga.

Pipe Size 

20 or 25 mm Nom.

Max Single Pipe Length 

123 m  *other three pipes disabled

Total Pipe Length 

320 m  * designs  must  be  verified  within 

PipeIQ software

Shipping Weight 

5.4 kg

Net weight  

4.9 kg

EN54 Ratings

Max. Single pipe length:  

120 m

Max. branched pipe length:  

480 m

Max. number of holes: 

Class A: 40

 

Class B: 40

 

Class C: 60

Содержание 9400XE FAAST

Страница 1: ...R FLOW DISPLAY 6 FAULT DISPLAY 6 LCD USER INTERFACE 7 HOME SCREEN 7 MAIN MENU SCREEN 8 Active Faults 8 Air Flow 8 Functions 8 CONFIGURATION GENERAL SETTINGS 8 Network 9 Email Menu 9 Modbus 9 Alarm Set...

Страница 2: ...ary audible indicator ITEMS INCLUDED WITH UNIT FAAST XT unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable EMI Filter Assembly PipeIQ software comprehensi...

Страница 3: ...e unit to match the orien tation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the uni...

Страница 4: ...power supply used with FAAST XT must be EN54 4 approved The system requires an EMI line filter in order to meet CE certification to CISPR22 specifications The EMI line filter in cluded needs to be co...

Страница 5: ...is desired 9 Verify the system fan starts up and air begins to flow out of the exhaust port The user interface will provide the device status 10 The device will establish an airflow baseline during t...

Страница 6: ...every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the cu...

Страница 7: ...isplay under the Active Faults menu The possible fault conditions are as follows TYPE DESCRIPTION ACTIVATED RELAY Low Flow Fault Device has decrease airflow as defined by the user program mable bounda...

Страница 8: ...t mode When this function is selected from the functions menu the device will ask for confirmation Use the scroll rs keys to select cancel or ok and then the select 8 key to confirm the selection SOUN...

Страница 9: ...TIME OUT The Time Out information set for the unit is displayed DIAGNOSTIC Information on system diagnostics is displayed SPECIAL MODE SCREENS Special mode screens are displayed temporarily when a spe...

Страница 10: ...that relay To remove the device from test a RESET must be done SOUNDER TEST The sounder test function can be accessed via the LCD user interface Upon initiation the device will exercise the selected s...

Страница 11: ...Ethernet networking equipment Connectivity is provided by an onboard RJ 45 connector located on the bottom of the unit The network interface is required for initial detector configuration Once initial...

Страница 12: ...s the authority to increase or alter the obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke de...

Отзывы: