ID
Property name
Setting value
20253 1
CPU: Name [1]
Blank
I/O Interface Unit CJ1W-II101
PLC Box
Set the PLC box setting values as follows.
ID
Property name
Setting value
20161
Configuration project
Same value as "Configuration project" of the CPU
Unit
20408
Station ID
Same value as "Station ID" of the CPU Unit
20427
Rack ID
Rack number
20410
PLC card is placed on rack ID
Blank
20411
Position (slot / module)
Blank
20253 1
CPU: Name [1]
Same value as "CPU: Name [1]" of the CPU Unit
Precautions for Correct Use
To import a CJ-series Unit configuration, you need to set this as follows.
• Set rack numbers so that they are sequential numbers that start from 1.
• Set not more than three CJ1W-II101 Units for one CPU Unit.
CJ-series Units in an Expansion Rack Configuration (Excluding I/O
Interface Units)
PLC Box
Set the PLC box setting values as follows.
ID
Property name
Setting value
20161
Configuration project
Same value as "Configuration project" of the CPU Unit
20408
Station ID
Same value as "Station ID" of the CPU Unit
20427
Rack ID
Blank
20410
PLC card is placed on rack ID
Same value as "Rack ID" of the CJ1W-II101 to which the CJ-
series Unit belongs
20411
Position (slot / module)
Slot number
20253 1
CPU: Name [1]
Same value as "CPU: Name [1]" of the CPU Unit
20418
Version
Version (This must be a version that exists in the Sysmac Stu-
dio and a single-byte number that contains periods as the de-
limiter. To specify the version of a Unit whose version is indicat-
ed as "---" on the Sysmac Studio, set "---" or "0.0".)
If blank, the component data will be imported with the latest
version.
3 Setting EPLAN Electric P8
3-13
Sysmac Studio Electrical CAD Connector Function Practices Guide for AutomationML Import (EPLAN Electric P8) (P156)
3-3 Setting the Project
3
3-3-4
CJ-series Units
Содержание SYSMAC-SE2