50
Circular Operating Mode: Functioning as Mechanical Cam Switches System Configuration
Counter Unit
C200H PC
An encoder adapter is required
if the C200H-CT002 is used
with an open-collector encoder.
Motor
Encoder
Inputs A, B, and Z
Outputs #1, #6, and #7
Encoder adapter
Operation
This example system uses the encoder to detect control timing for devices
linked to a shaft driven by a motor. The system controls outputs according to
shaft rotation.
Switch Settings
In this example, the unit number selector is set to 1 and the mode selector is
set to 2. Pins 2, 4, 6, and 8 are turned ON on the back panel DIP switch to
designate offset phase inputs with a x 4 input multiplier and to enable reset-
ting on the rising edge of input Z or RESET COUNTER, whichever is set last
(both must be ON to reset the Counter Unit). All other pins are turned OFF.
Wiring
1, 2, 3... 1.
Connect encoder outputs to inputs A, B, and Z.
2.
Connect outputs #1, #6, and #7 to controllers for devices linked to the
shaft.
Linear and Circular Modes
Section 4-2
Содержание SYSMAC C200H-CT001-V1
Страница 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ......
Страница 10: ......
Страница 20: ......
Страница 46: ......
Страница 96: ......
Страница 98: ......