![Omron SYSMAC C200H-CT001-V1 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/omron/sysmac-c200h-ct001-v1/sysmac-c200h-ct001-v1_operation-manual_742017023.webp)
9
This switch must be set before the Counter Unit is mounted. It is not neces-
sary to set all the pins for all operating modes. Refer to 3-2 Input Selection
and Section 4 Data Allocation and Operating Modes for operational details.
1
2
3
Input type
OFF OFF OFF
OFF OFF
OFF
OFF
ON
ON
ON
ON
ON
*
*
*
Normal
x2
x4
Up and down pulses
Pulse and direction
Offset phases
1
2
3
4
5
6
7
8
ON
Input Selection
Pins 1 through 3 are used to select the type
of inputs for inputs A and B.
4
5
Function
OFF
ON
ON
ON
Input Z effective on falling edge.
Input Z effective on rising edge.
OFF
Input Z inoperative
*
For Operating Mode 1 or 2: Input Z
6
7
Function
OFF
ON
ON
ON
Control input IN1 effective on
falling edge.
Control input IN1 effective on
rising edge.
OFF
Control input IN1 inoperative
*
This setting is effective only for operating
modes 1,2, and 3.
In modes 4, 5, and 6, control inputs IN1 and IN2
are always effective on their rising edges
8
Function
ON
Reset bit effective on rising edge.
OFF Reset bit inoperative
This setting is effective only for operating
modes 1,2, and 3.
Control Input IN1
Internal Reset Bit
4
5
Function
*
ON
Start on control input IN2.
OFF
Start on START command
(IR n, bit 00).
*
For Operating Mode 3: Start Input
*Pins marked with asterisks are not used.
Back Panel DIP Switch
Switch Settings
Section 2-1
Содержание SYSMAC C200H-CT001-V1
Страница 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ......
Страница 10: ......
Страница 20: ......
Страница 46: ......
Страница 96: ......
Страница 98: ......