66
C200H-RT202
+
–
LG
GR
24 VDC
RUN output
Connect to independent ground to
prevent shock.
Connect to independent ground to reduce
noise interference and prevent shock.
ON while the system is operating.
Use a 24-VDC power supply.
NC
NC
NC
NC
Fuse
*
* The LG and GR terminals are
connected internally.
7.3
M3.5
3 max.
Terminals
Use thick cables (1.25 mm
2
min.) to prevent against voltage drops.
M3.5 self-rising terminals screws are used for the terminal block. When wir-
ing to the terminal block, use crimp terminals for M3.5 screws. Do not con-
nect stranded wires directly to the terminal block.
Tighten the screws on the terminal block to a torque of 0.8 N
S
m.
Power Supply Wiring
Precautions
Wiring
Section 5-5