Masters and Slaves
Section 4-1
52
C200H Slaves indicators function together to show the status of the System.
The RUN indicator is controlled by the mode setting on the CPU Unit.
XMT/RCV
ERROR1
ERROR2
RUN
Status
Meaning
not lit
not lit
not lit
not lit
System not started or pow-
er off.
Master is still testing System or power off.
Power has not yet been turned on.
flash
not lit
not lit
---
Normal transmission
Normal transmissions are occurring be-
tween Slave and Master.
---
lit
---
not lit
Transmission error
Error has occurred in transmissions with
Master.
---
lit
lit
not lit
I/O bus error
Error has occurred in I/O bus connecting
Slaves to I/O Units.
flash
flash
lit
---
I/O verification error
An I/O Unit configuration of Slave Rack
has changed.
flash
lit
lit
not lit
I/O setting error
An I/O Unit designation on the Slave Rack
is wrong.
flash
lit
flash
---
Expansion I/O Rack miss-
ing.
An Expansion I/O Rack connected to the
Slave Rack with I/O Connecting Cable
cannot be confirmed by the PC.
The DIP switch and terminator selectors are accessed by removing the
switch cover on the front of the Slave. Use a regular screwdriver to open the
cover if necessary. Always be sure that the PC and Slave power are turned
off before setting the switches.
Terminator Selector
Terminator
(Termination resistance ON)
Not terminator
(Termination resistance OFF)
Terminator Setting
DIP Switch
Pins 1 through 3: Unit Number
Unit number*
Pin 1
2
3
0
OFF
OFF
OFF
1
OFF
OFF
ON
2
OFF
ON
OFF
3
OFF
ON
ON
4
ON
OFF
OFF
5
ON
OFF
ON
6
ON
ON
OFF
7
ON
ON
ON
*Unit numbers 0 and 1 can be set for C120 and C500 Systems; unit numbers
0 through 4 for C200H Systems; and 0 through 7 for C1000H and C2000H
Systems.
Indicators
C200H Slave Switches
Содержание SYSMAC C-series
Страница 1: ...Cat No W120 E1 08 Wired Remote I O SYSMAC C series Rack PCs...
Страница 2: ...Wired Remote I O System Manual Revised April 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 130: ...Cat No W120 E1 08 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 131: ...Cat No W120 E1 08 SYSMAC C series Rack PCs Wired Remote I O SYSTEM MANUAL...