92
CONTINUE and STOP Mode Operation
Section 7-4
7-4
CONTINUE and STOP Mode Operation
The following tables can be compared and contrasted to understand differ-
ences between CONTINUE and STOP mode operation. These modes are
set on Masters. Refer to Subsection 4-1 for setting details.
The following configuration and table will be used to show LED indications
when power to Slave #0 is interrupted in CONTINUE mode. Refer to Section
2 for details on indicator operation.
C500 CPU Rack
C500 Master
C500 Slave
Slave #0
C500 Slaves
Slave #1 Terminator
Condition
C500 LEDs
LEDs on Master
LEDs on
Slave #0
LEDs on
Slave #1
POWER
RUN
ERROR
ALARM OUT IN
TR/
ERR
TEST
OK
END RS
CHECK
LINE
ERR
TR/
ERR
ERR
TR/
ERR
ERR
Normal
operation
lit
lit
not lit
not lit
not lit
flash not lit
not lit
not lit flash
not lit
flash
not lit
Power in-
terruption
to Slave
#0
lit
lit
not lit
lit
not lit
lit
not lit
not lit
not lit not
lit
not lit
flash
not lit
Remote I/O error occurs; operation continues.
Word 59 contains “#B008.”
Transmission error occurs;
transmission to Slave #1 con-
tinues.
Power inter-
rupted.
Normal op-
eration.
Power re-
stored to
Slave #0
lit
lit
not lit
lit
not lit
flash not lit
not lit
not lit flash
not lit
flash
not lit
1. All ALARM LEDs turned off by performing
recovery operation from Programming
Console.
2. Remote I/O Error flag cleared by turning
Error Check flag ON, then OFF again.
Normal operation
Normal operation
Operations in CONTINUE
Mode
Содержание SYSMAC C-series
Страница 1: ...Cat No W120 E1 08 Wired Remote I O SYSMAC C series Rack PCs...
Страница 2: ...Wired Remote I O System Manual Revised April 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 130: ...Cat No W120 E1 08 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 131: ...Cat No W120 E1 08 SYSMAC C series Rack PCs Wired Remote I O SYSTEM MANUAL...