![Omron SYSMAC C-series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/omron/sysmac-c-series/sysmac-c-series_system-manual_743584050.webp)
!
39
Setting Procedure
Section 3-3
Restrictions placed on Systems combining C500 Masters and C200H Slaves
depend on the PC to which the Master(s) is mounted. Refer to 2-1 Basic Sys-
tem for details.
16 pts.
16 pts.
16 pts.
16 pts.
32 pts.
64 pts.
16 pts.
IR 20
IR 19
IR 8
IR 7
IR 5 & 6
IR 1, 2, 3, & 4
IR 0
IR 13
IR 12
IR 11
IR 10
IR 9
IR 18
IR 17
IR 16
IR 15
IR 14
C500 Master
C1000H PC
C200H Slave
C200H Slave
Set to Unit #0 and
to Master other
than C200H.
Set to Unit #1, to
Master other than
C200H, and as ter-
minator.
Caution
When C200H Slave Racks are connected to Masters on PCs other than the
C200H/C200HS, all Output Units on these Slave Racks will be treated as having
at least 16 output points. disabling the Fuse-burnout and Alarm Detection Bits on
Units that normally provide them (e.g., C200H-OD411, C200H-OD213,
C200H-OD214, and C200H-OA221).
When using the C200H Backplane for 10 slots as a remote I/O Slave for the
CVM1/CV500/CV1000/CV2000, only the 8 slots from the left can be used; the
9th and 10th slots from the left cannot be used.
3-3
Setting Procedure
Set the Units in the following order. This procedure must be carried out
whenever Masters, Slaves, or Remote Terminals are added to the System.
1.
Turn off the power, set the unit numbers of the Slaves and check the last
I/O word being used by the PC. For a C1000H or C2000H System, al-
ways set Slave unit numbers in order starting from number 0. (See
Maximum Number of Connectable Units under 2-1 Basic System.)
2.
Set Remote Terminal words so that no words being used by the PC are
used again. Also, do not set more than the available number of words.
Doing so will result in an I/O error.
3.
Connect the 2-conductor cables starting from each Master and working
out to each Unit that will be a terminator. Be sure to connect positive to
positive, negative to negative.
C1000H Example
1, 2, 3...
Содержание SYSMAC C-series
Страница 1: ...Cat No W120 E1 08 Wired Remote I O SYSMAC C series Rack PCs...
Страница 2: ...Wired Remote I O System Manual Revised April 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 130: ...Cat No W120 E1 08 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 131: ...Cat No W120 E1 08 SYSMAC C series Rack PCs Wired Remote I O SYSTEM MANUAL...