60
5-1-5
Link Adapters
10
135
130
43
150
165
4.5
7
Mounting hole
dimensions
63
140
Use thick cables (1.25 mm
2
min.) to prevent against voltage drops.
M4 self-rising terminals screws are used for the terminal block. When wiring
to the terminal block, use crimp terminals for M4 screws. Do not connect
stranded wires directly to the terminal block.
Tighten the screws on the terminal block to a torque of 1.2 N
S
m.
5-2
Differentiating Units
Nameplate, LED, and relay case colors are used to differentiate between In-
put and Output Blocks and between AC and DC Input Blocks as shown in the
following table.
---
Nameplate
LEDs
Relay Case
Input Blocks
(DC)
Red
Green
Green
(AC)
Red
Red
Red
Output Block
(DC)
Yellow
Green
Clear
I/O Block nameplates are color matched with PC I/O Units.
LED positions and relay orientation also differ between Input and Output
Blocks and can be used to differentiate between them. Relays are also posi-
tioned to assist in following signal flow.
Power Supply Wiring
Precautions
Differentiating Units
Section 5-2