Remote Terminal
Section 4-2
54
Remove the switch cover to access the DIP switch and terminator switch. Set
these as shown below. The switch cover is in a slightly different position on
G72C Remote Terminals.
+
–
Pins 1 to 6
ON (right):
Terminator
OFF (left):
All others
Word numbers are computed as binary numbers with pins 1 through 5 repre-
senting the one’s place though the 16’s place. For example, turning on all five
pins would set word 31, i.e., 2
0
+ 2
1
+ 2
2
+ 2
3
+ 2
4
= 1 + 2 + 4 + 8 + 16 = 31.
Pin 5 must be set OFF for all Remote Terminals, in C120 Systems, i.e., the
highest word that can be set is 15.
The word actually allocated to a Remote Terminal depends on the PC that
controls it and is computed as shown in the following table.
PC
Allocated word
C120 and C500
Same as switch setting
C1000H and C2000H
32 x word multiplier of switch setting
C200H
Switch s 200
Pin 6: Output HOLD/STOP Mode
OFF: STOP mode
All output words set to OFF for transmission errors.
ON: HOLD mode
All output words retain status for transmission errors.
Transmission errors for Remote Terminals are the same as those for Slaves.
Switches
Pins 1 to 5: Word Setting
Содержание SYSMAC C-series
Страница 1: ...Cat No W120 E1 08 Wired Remote I O SYSMAC C series Rack PCs...
Страница 2: ...Wired Remote I O System Manual Revised April 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 130: ...Cat No W120 E1 08 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 131: ...Cat No W120 E1 08 SYSMAC C series Rack PCs Wired Remote I O SYSTEM MANUAL...