2-23
D
Installing a Noise Filter on the Output Side
Connect a Noise Filter to the output side of the Inverter to reduce radio noise and induc-
tion noise.
Power
supply
3G3JV
SYSDRIVE
3G3IV-PLF
Noise
Filter
Signal line
Induction noise
Radio noise
Controller
AM radio
Induction Noise:
Electromagnetic induction generates noise on the signal line, caus-
ing the controller to malfunction.
Radio Noise:
Electromagnetic waves from the Inverter and cables cause the
broadcasting radio receiver to make noise.
D
Countermeasures against Induction Noise
As described previously, a Noise Filter can be used to prevent induction noise from be-
ing generated on the output side. Alternatively, cables can be routed through a
grounded metal pipe to prevent induction noise. Keeping the metal pipe at least 30 cm
away from the signal line considerably reduces induction noise.
Power supply
3G3JV
SYSDRIVE
Metal pipe
30 cm min.
Signal line
Controller
Design
Chapter 2
Содержание SYSDRIVE 3G3JV-AB001
Страница 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Страница 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Страница 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 62: ...4 10 Test Run Chapter 4...
Страница 131: ...7 22 Maintenance Operations Chapter 7...
Страница 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Страница 138: ...Chapter 9 List of Parameters 9...
Страница 150: ...Chapter 10 Using the Inverter for a Motor 10...
Страница 165: ...Revision History 10 2...
Страница 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...