6-7-3 Momentary Power Interruption Compensation
(n47)
•
The parameter specifies the processing that will be performed when a momentary
power interruption occurs.
n47
Momentary Power Interruption
Compensation
Changes during
operation
No
Setting
range
0 to 2
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Disabled. (An undervoltage fault will be detected when there is momentary
power interruption for 15 ms or more.)
1
The Inverter will continue operating if power is restored within 0.5 s.
(see note 1)
2
The Inverter will restart when power is restored. (see note 2)
Note 1. An undervoltage warning is detected with the parameter set to 1. The Inverter
will restart after speed searching if power is restored within 0.5 s. If power failure
continues for more than 0.5 s, undervoltage fault 1 will be detected.
Note 2. No undervoltage warning is detected with the parameter set to 2. The Inverter
will restart after speed searching when power is restored.
6-7-4 Fault Retry (n48)
Caution
The Inverter may be break if the fault retry function is used.
If the Inverter breaks, take the following measures:
Be sure to install a no-fuse breaker (NFB).
Provide the Inverter and peripheral machines with a sequence so
that the machines will stop operating when the Inverter has an op-
erational fault.
•
The fault retry function automatically resets and restarts the Inverter in the case the
Inverter has an overvoltage fault, overcurrent fault, or ground fault.
•
In the case of any other fault, the protective function operates instantly and the fault
retry function does not operate.
•
This function is to be used only if the user does not want to interrupt the mechanical
system, even if this function may damage the Inverter.
•
Set n40 for multi-function output to the following value so that external overtorque
detection output will be turned on.
Set value: 14 for fault retries
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3JV-AB001
Страница 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Страница 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Страница 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 62: ...4 10 Test Run Chapter 4...
Страница 131: ...7 22 Maintenance Operations Chapter 7...
Страница 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Страница 138: ...Chapter 9 List of Parameters 9...
Страница 150: ...Chapter 10 Using the Inverter for a Motor 10...
Страница 165: ...Revision History 10 2...
Страница 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...