![Omron SYSDRIVE 3G3JV-AB001 Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/omron/sysdrive-3g3jv-ab001/sysdrive-3g3jv-ab001_user-manual_742834128.webp)
7-19
H
Periodic Inspection
Check the following items during periodic maintenance.
Before beginning inspection, be sure to turn off the power supply. Confirm that all the
indicators on the front panel have turned off, and then wait until at least 1 minute has
elapsed before beginning the inspection.
Be sure not to touch the terminals right after the power has been turned off. Otherwise,
an electric shock may occur.
•
The terminal screws of the Inverter should not loose.
•
There should be no conductive dust or oil mist on the terminal block or inside the Invert-
er.
•
The mounting screws of the Inverter should not be loose.
•
No dirt or dust should be accumulating on the radiation fin.
•
No dust should be accumulating on the vents of the Inverter.
•
There should be no abnormalities in the outward appearance of the Inverter.
•
There should be no unusual noises or vibration and the accumulated operating time
should not exceeded the specifications.
H
Periodic Maintenance Parts
Periodic inspection standards vary with the installation environment and usage condi-
tions of the Inverter.
The maintenance periods of the Inverter are described below. Keep them as reference.
Maintenance Periods (Reference)
S
Cooling fan:
2 to 3 years
S
Electrolytic capacitor:
5 years
S
Fuse:
10 years
The usage conditions are as follows:
S
Ambient temperature:
40
j
C
S
Load factor:
80%
S
Operation:
8 hours per day
S
Installation:
According to instructions in manual
It is recommended that the ambient temperature and power-on time be reduced as
much as possible to extend of the life of the Inverter.
Note For details regarding maintenance, consult your OMRON representative.
H
Replacement of Cooling Fan
If the FAN fault is displayed or the cooling fan needs replacement, take the following
steps to replace it.
Maintenance Operations
Chapter 7
Содержание SYSDRIVE 3G3JV-AB001
Страница 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Страница 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Страница 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 62: ...4 10 Test Run Chapter 4...
Страница 131: ...7 22 Maintenance Operations Chapter 7...
Страница 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Страница 138: ...Chapter 9 List of Parameters 9...
Страница 150: ...Chapter 10 Using the Inverter for a Motor 10...
Страница 165: ...Revision History 10 2...
Страница 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...