![Omron NX-EC0112 Скачать руководство пользователя страница 376](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777376.webp)
10 Troubleshooting
10 - 22
NX-series Position Interface Units User’s Manual (W524)
Event name
SSI Communications Error
Event code
84D00000 hex
Meaning
An error occurred in SSI communications.
Source
Depends on where the Sysmac Stu-
dio is connected and the system con-
figuration.
Source details
NX Unit
Detection
timing
Continuously
Error
attributes
Level
Observation
Recovery
Restart the NX
Unit.
Log category
System
Effects
User program
Continues.
Operation
The previous value is retained as the present
value data and the data is not updated.
The following bit changes to TRUE: Ch
SSI
Communications Error Status bit in the SSI Sta-
tus.
This bit returns to FALSE the next time normal
SSI communications are performed.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The SSI data settings do not agree
with the SSI communications settings
in the connected device.
Make the settings so that the SSI
data settings and the SSI com-
munications settings agree.
Make the settings so that the
SSI data settings and the SSI
communications settings agree.
The wiring between the NX Unit and
the connected device is not correct or
disconnected.
Check the wiring between the
NX Unit and the connected
device and correct any problems
that are found.
Make sure that the wiring
between the NX Unit and the
connected device is correct.
Noise
Implement noise countermea-
sures if there is excessive noise.
Implement noise countermea-
sures if there is excessive
noise.
Attached
information
Attached information 1: Error channel
1: Channel 1
2: Channel 2
Attached information 2: Error details
1: Preparations for communications are not completed.
2: Frame error
3: Parity error
4: Communications timeout
5: Out of range for position difference
Precautions/
Remarks
You can change the event level to the minor fault level. If you change the level to the minor fault level, the
Recovery column above will be changed to “Reset error in the NX Unit.”
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...