![Omron NX-EC0112 Скачать руководство пользователя страница 197](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777197.webp)
6 - 71
6 Incremental Encoder Input Units
NX-series Position Interface Units User’s Manual (W524)
6-
9 Fu
nct
ion
s
6
6-
9-1
1 Pulse Period Measuremen
t
If pulse period measurement is enabled, measurement of the period measurement value is started from
the first detected edge.
After measurement is started, the period measurement value is updated every time a target edge is
detected.
The internal Unit counter for the pulse period measured value is a ring counter. When the upper limit
value for the counter (2,147,483,647) is reached, an overflow flag is set and the count value returns to
0 before its counting is continued.
If pulse period measurement is disabled when the power is turned ON or when the Unit is restarted, the
pulse period measured value will be 0.
The following three bits are used to control pulse period measurement
Pulse Period Measurement Function
on page 6-41 for information on the bit configuration of
the Pulse Period Measurement Function parameter.
Setting Flags and Parameters
Flag name
Function
Operation
Pulse Period Measurement Enable
Enables or disables pulse period
measurement.
*1
0: Disable
1: Enable
*1. If the Edge Detection Method parameter is set to disable (0) pulse period measurement, the function is dis-
abled regardless of the setting of this bit.
When Enabled (0 to 1)
• The Pulse Period Measurement
Enabled bit is set.
• The Pulse Period Measured
Value is reset to 0.
• The Pulse Period Measurement
Value Overflow Flag is reset.
When Disabled (0)
• The Pulse Period Measurement
Enabled bit is reset.
• The Pulse Period Measured
Value is set to 0.
• The Pulse Period Measurement
Value Overflow Flag is reset.
Pulse Period Measurement Value
Clear
Clears the Pulse Period Measured
Value.
0 to 1: Value cleared.
*2
*2. This bit is valid when the Pulse Period Measurement Function is enabled.
When Enabled (0 to 1)
• The Pulse Period Measured
Value is reset to 0.
• The Pulse Period Measurement
Value Overflow Flag is reset.
• When the above processing is
completed, the Pulse Period
Measurement Value Clear Com-
pleted bit is set.
*3
*3. Reset this bit to reset the Pulse Period Measurement Value Clear Completed bit.
Pulse Period Measurement Value
Overflow Flag Clear
Resets the Pulse Period Measure-
ment Value Overflow Flag.
0 to 1: Flag reset.
*2
When Enabled (0 to 1)
• The Pulse Period Measurement
Value Overflow Flag is reset.
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Страница 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Страница 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...