K6EL

Ground Fault Relay Characteristics

Note:

The range for an operating time of 0.3 s is 0.15 to 0.45 s and the range for an operating time of 0.8 s is 0.6 to 1.2 s.

ZCT (Zero-phase Current Transformer)

Note:

Do not connect ZCT output terminals k and l to ground. Doing so may result in damage to the Relay.

Item

Type

High-speed models

Delayed models

Delayed high-sensitivity models

Operating time

Less than 0.1 s

0.3 s/0.8 s (switchable)

Less than 0.5 s

Inertial non-operating 
time

---

0.1 s when set to 0.3 s
0.5 s when set to 0.8 s

Control power supply 
range

80% to 110% of the control power supply voltage

Operating temperature 
range

10 to 55 

q

C (with no icing)

Operating humidity 
range

45% to 85% (with no condensation)

Insulation resistance

5 M

:

 min. at 500 VDC (between charged parts and the mounting panel)

Dielectric strength

1,500 VAC, 50/60 Hz for 1 min (between charged parts and the mounting panel)

Lightning impulse 
dielectric strength

1.2/50

P

s, 7,000 V (between control power supply terminals)

Lightning impulse 
operation failure

1.2/50

P

s, 7,000 V (primary side of ZCT)

Vibration resistance

Destruction: 16.7 Hz, 4-mm double amplitude for 1 min 

Shock resistance

98 m/s

2

Item

Structure

Indoor through-type models

Indoor separate-type models

Model

OTG-L21

OTG-L30

OTG-L42

OTG-L68

OTG-L82

OTG-L156

OTG-CN52

OTG-CN77

OTG-

CN112

Rated current

50 A

100 A

200 A

400 A

600 A

1,000 A

200 A

400 A

600 A

Diameter of 
through-hole

21 mm

30 mm

42 mm

68 mm

82 mm

156 mm

52 mm

77 mm

112 mm

Rated voltage

600 VAC max., 50/60 Hz, single-phase/three-phase

Output terminal 
polarity

None (The ZCT’s output terminals k and l can be connected to either input terminals 3 or 4 of the Relay.) (See note.)

Insulation 
resistance

100 M

:

 min. (between charged metal parts and ground)

Dielectric strength

2,200 VAC, 50/60 Hz for 1 min (between charged metal parts and ground)

Ambient operating 
temperature

10 to 60 

q

C (with no icing)

Weight

Approx. 
90 g

Approx. 
130 g

Approx. 
230 g

Approx. 
480 g

Approx. 
700 g

Approx. 
6.6 kg

Approx. 
1.3 kg

Approx. 
2.5 kg

Approx. 
3.5 kg

Содержание K6EL

Страница 1: ...Number Structure Model Number Legend 1 Ground Fault Relay 2 Operating Time and Reset Method None 0 1 s manual reset A 0 3 0 8 s switchable manual reset R 0 5 s automatic reset 3 Sensed Current 30 30...

Страница 2: ...OK OK OTG L30 100 A OK OK OTG L42 200 A OK OK OTG L68 400 A OK OTG L82 600 A OK OTG L156 1 000 A OK OTG CN52 200 A OK OTG CN77 400 A OK OTG CN112 600 A OK Model Y92F 30 Y92F 71 Model Y92A 48B Hard Co...

Страница 3: ...arts and the mounting panel Lightning impulse dielectric strength 1 2 50 Ps 7 000 V between control power supply terminals Lightning impulse operation failure 1 2 50 Ps 7 000 V primary side of ZCT Vib...

Страница 4: ...110 V See note 1 See note 2 Operation at 200 220 V Note 1 The K6EL R50 does not have terminals 6 and 7 2 The K6EL R500 and K6EL R50 do not have terminal 2 They cannot be used at 200 220 V POWER SENSIT...

Страница 5: ...wise indicated Ground Fault Relay Load Y b Auxiliary relay Alarm buzzer 100 110 VAC 200 220 VAC Y BZ Transformer Molded case circuit breaker 6 5 4 3 2 1 11 10 9 8 7 kt k l lt OTG ZCT K6EL Ground Fault...

Страница 6: ...te Recommended panel thickness 1 to 3 2 mm Y92F 30 Flush Mounting Adapter Sold Separately Y92F 71 Flush Mounting Adapter Sold Separately P2CF 11 sold separately PL11 sold separately 103 K6EL 77 7 16 K...

Страница 7: ...pitch 136 68 dia 118 17 31 9 3 11 6 1 Mounting Hole Cutout Dimensions Two 5 dia holes or two M4 screw holes 97 107 97 mounting pitch 25 109 88 17 42 dia 11 9 3 5 2 Mounting Hole Cutout Dimensions kt k...

Страница 8: ...7 Mounting Hole Cutout Dimensions 9 263 156 dia 138 3 2 270 230 60 M5 terminal screws 130 90 20 40 L 230 90 Mounting Hole Cutout Dimensions Four 8 5 dia holes or four M8 screw holes K K M4 terminal sc...

Страница 9: ...2 325 mm2 325 mm2 250 mm2 OTG L82 600 A 82 dia 500 mm2 500 mm2 400 mm2 400 mm2 OTG L156 1 000 A 156 dia 500 mm2 500 mm2 1 000 mm2 1 000 mm2 OTG CN52 200 A 52 dia 200 mm2 200 mm2 150 mm2 100 mm2 OTG CN...

Страница 10: ...as possible or use a shield line When installing a separate type ZCT with current flowing along the primary conductors short the secondary terminals using clips or some other method Switching the Sen...

Страница 11: ...as for calculating ground currents for complete ground faults Depending on the location the allowable ground fault current may be restricted In this case use values of R and C that do not exceed the r...

Страница 12: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syste...

Отзывы: