K6EL

ZCTs (Zero-phase Current Transformers)

Ground Fault Relay and ZCT Combinations

(OK: Compatible)

Note: 1.

“OK” indicates groupings that can be combined freely.

2.

Combinations with the OTG-LA

@@

 are also possible.

Options

Flush Mounting Adapters

Front Cover 

Specifications

Ground Fault Relay Ratings

Note: 1.

The K6EL-R50 requires a 100-VAC control power supply.

2.

Only the K6EL-R50 can be switched between 50 mA 

r

10% and 150 mA 

r

20%.

Rated current

Type

Indoor through-type models

Indoor separate-type models

Sensed current

Model

Diameter of through-hole

Model

Diameter of through-hole

50 A

OTG-L21

21 mm

---

---

100 A

OTG-L30

30 mm

---

22 mm

200 A

OTG-L42

42 mm

OTG-CN52

52 mm

400 A

OTG-L68

68 mm

OTG-CN77

77 mm

600 A

OTG-L82

82 mm

OTG-CN112

112 mm

1,000 A

OTG-L156

156 mm

---

---

ZCT

Ground Fault Relay

K6EL-30

K6EL-R50

K6EL-100, -200, -500, -R500

K6EL-A100, -A200, -A500

OTG-L21 (50 A)

OK

OK

OTG-L30 (100 A)

OK

OK

OTG-L42 (200 A)

OK

OK

OTG-L68 (400 A)

---

OK

OTG-L82 (600 A)

---

OK

OTG-L156 (1,000 A)

---

OK

OTG-CN52 (200 A)

---

OK

OTG-CN77 (400 A)

---

OK

OTG-CN112 (600 A)

---

OK

Model

Y92F-30

Y92F-71

Model

Y92A-48B (Hard Cover)

Y92A-48D(Soft Cover)

Item

Type

High-speed models

Delayed models

Delayed high-sensitivity 

models

Control power supply

100/110 VAC or 200/220 VAC, 50/60 Hz (same for all) (See note 1.)

100 VAC

Rated current

Depends on the ZCT

Sensed current

50% to 100% of the rated sensed current (50 mA

r

10%, 150 mA 

r

20%) (See note 2.)

Non-operating current

0% to 50% of the rated sensed current

Rated short-time current

2,500 A

Ground fault indication method

LED (red)

Test method

Relay operation confirmed using a test button. (Independent of ZCT connection.)

Reset method

Manual

Either press the reset button or turn the control power supply OFF and ON again.

Automatic

Automatically resets when the ground fault is cleared.

Built-in 
contacts

Contact form

SPDT+SPST-NO

SPDT

Carrying current

5 A

3 A

Rated load

cos

I

 = 1

cos

I

 = 0.4 (L/R = 7 ms)

cos

I

 = 1

240 VAC

5 A

2 A

220 VAC, 3 A

110 VDC

0.3 A

0.2 A

30 VDC

5 A

3 A

Power (VA) consumption

3 VA  max.

Weight

Approx. 110 g

Содержание K6EL

Страница 1: ...Number Structure Model Number Legend 1 Ground Fault Relay 2 Operating Time and Reset Method None 0 1 s manual reset A 0 3 0 8 s switchable manual reset R 0 5 s automatic reset 3 Sensed Current 30 30...

Страница 2: ...OK OK OTG L30 100 A OK OK OTG L42 200 A OK OK OTG L68 400 A OK OTG L82 600 A OK OTG L156 1 000 A OK OTG CN52 200 A OK OTG CN77 400 A OK OTG CN112 600 A OK Model Y92F 30 Y92F 71 Model Y92A 48B Hard Co...

Страница 3: ...arts and the mounting panel Lightning impulse dielectric strength 1 2 50 Ps 7 000 V between control power supply terminals Lightning impulse operation failure 1 2 50 Ps 7 000 V primary side of ZCT Vib...

Страница 4: ...110 V See note 1 See note 2 Operation at 200 220 V Note 1 The K6EL R50 does not have terminals 6 and 7 2 The K6EL R500 and K6EL R50 do not have terminal 2 They cannot be used at 200 220 V POWER SENSIT...

Страница 5: ...wise indicated Ground Fault Relay Load Y b Auxiliary relay Alarm buzzer 100 110 VAC 200 220 VAC Y BZ Transformer Molded case circuit breaker 6 5 4 3 2 1 11 10 9 8 7 kt k l lt OTG ZCT K6EL Ground Fault...

Страница 6: ...te Recommended panel thickness 1 to 3 2 mm Y92F 30 Flush Mounting Adapter Sold Separately Y92F 71 Flush Mounting Adapter Sold Separately P2CF 11 sold separately PL11 sold separately 103 K6EL 77 7 16 K...

Страница 7: ...pitch 136 68 dia 118 17 31 9 3 11 6 1 Mounting Hole Cutout Dimensions Two 5 dia holes or two M4 screw holes 97 107 97 mounting pitch 25 109 88 17 42 dia 11 9 3 5 2 Mounting Hole Cutout Dimensions kt k...

Страница 8: ...7 Mounting Hole Cutout Dimensions 9 263 156 dia 138 3 2 270 230 60 M5 terminal screws 130 90 20 40 L 230 90 Mounting Hole Cutout Dimensions Four 8 5 dia holes or four M8 screw holes K K M4 terminal sc...

Страница 9: ...2 325 mm2 325 mm2 250 mm2 OTG L82 600 A 82 dia 500 mm2 500 mm2 400 mm2 400 mm2 OTG L156 1 000 A 156 dia 500 mm2 500 mm2 1 000 mm2 1 000 mm2 OTG CN52 200 A 52 dia 200 mm2 200 mm2 150 mm2 100 mm2 OTG CN...

Страница 10: ...as possible or use a shield line When installing a separate type ZCT with current flowing along the primary conductors short the secondary terminals using clips or some other method Switching the Sen...

Страница 11: ...as for calculating ground currents for complete ground faults Depending on the location the allowable ground fault current may be restricted In this case use values of R and C that do not exceed the r...

Страница 12: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syste...

Отзывы: