K6EL

Test Circuit

Select the resistance R shown in the test circuit diagram according to
the K6EL’s rated sensed current. Change the current using the slidac
and ascertain the K6EL’s operating value each time by reading the
ammeter.

For example, R could take the values shown below:
30 mA: 3.3 k

:

, 6 W

100 mA: 1 k

:

, 20 W

200 mA: 500

:

, 50 W

500 mA: 200

:

, 100 W

1,000 mA: 100

:

, 200 W

Safety Precautions

Correct Use

Installation and Wiring

Do not, under any circumstances, connect the ZCT’s output termi-
nals k and l to ground. Doing so may result in damage to the
Relay’s internal circuits.

Pass the primary conductor through the ZCT once.

The Relay detects ground faults in internal wiring of devices due to
insulation deterioration and so install the ZCT as close to the power
supply side as possible.

ZCT Installation

Install the ZCT at an outdoor cable inlet or on a ground bus bar at a
location allowing easy inspection.

When installing on the electrical path, use a ZCT with a value
greater than the electrical path’s rated current.

If the secondary lines run in parallel to a circuit carrying a large cur-
rent, either separate the lines as far as possible or use a shield line.

When installing a separate-type ZCT with current flowing along the
primary conductors, short the secondary terminals using clips or
some other method.

Switching the Sensed Current

1.

With the K6EL-

@

100, 200, 500, R50, and R500, the sensed cur-

rent can be switched using a flat-bladed screwdriver.

2.

The sensed current for the K6EL-30 is fixed and hence cannot be
switched.

Switching the Operating Time

1.

With the K6EL-A100, A200, and A500, the operating time can be
switched using a flat-bladed screwdriver.

2.

The operating time for the K6EL-30, 100, 200, 500, R50, and
R500 is fixed and hence cannot be switched.

Testing

If the ground fault indicator (red) lights when the Relay’s test button
is pressed, it means that the internal circuits are operating nor-
mally.

To make an overall test, run a simulated ground fault current.

Resetting

Once manual-reset models operate, they continue to operate until
they are reset. Reset them either by pressing the reset button
(black) or by turning the control power supply OFF and ON again.

Automatic-reset models reset automatically when the ground fault
is cleared (i.e., the current drops below the sensed current).

100 VAC

lt

l

k

kt

OTC

Switch

Slidac

mA

K6EL

Ammeter

R

ZCT

Run the secondary lines
close to each other.

K6EL

Separate by 20 cm min.

Primary conductor

Circuit carrying large current

Sensed current selection switch

Operating time selection switch

Содержание K6EL

Страница 1: ...Number Structure Model Number Legend 1 Ground Fault Relay 2 Operating Time and Reset Method None 0 1 s manual reset A 0 3 0 8 s switchable manual reset R 0 5 s automatic reset 3 Sensed Current 30 30...

Страница 2: ...OK OK OTG L30 100 A OK OK OTG L42 200 A OK OK OTG L68 400 A OK OTG L82 600 A OK OTG L156 1 000 A OK OTG CN52 200 A OK OTG CN77 400 A OK OTG CN112 600 A OK Model Y92F 30 Y92F 71 Model Y92A 48B Hard Co...

Страница 3: ...arts and the mounting panel Lightning impulse dielectric strength 1 2 50 Ps 7 000 V between control power supply terminals Lightning impulse operation failure 1 2 50 Ps 7 000 V primary side of ZCT Vib...

Страница 4: ...110 V See note 1 See note 2 Operation at 200 220 V Note 1 The K6EL R50 does not have terminals 6 and 7 2 The K6EL R500 and K6EL R50 do not have terminal 2 They cannot be used at 200 220 V POWER SENSIT...

Страница 5: ...wise indicated Ground Fault Relay Load Y b Auxiliary relay Alarm buzzer 100 110 VAC 200 220 VAC Y BZ Transformer Molded case circuit breaker 6 5 4 3 2 1 11 10 9 8 7 kt k l lt OTG ZCT K6EL Ground Fault...

Страница 6: ...te Recommended panel thickness 1 to 3 2 mm Y92F 30 Flush Mounting Adapter Sold Separately Y92F 71 Flush Mounting Adapter Sold Separately P2CF 11 sold separately PL11 sold separately 103 K6EL 77 7 16 K...

Страница 7: ...pitch 136 68 dia 118 17 31 9 3 11 6 1 Mounting Hole Cutout Dimensions Two 5 dia holes or two M4 screw holes 97 107 97 mounting pitch 25 109 88 17 42 dia 11 9 3 5 2 Mounting Hole Cutout Dimensions kt k...

Страница 8: ...7 Mounting Hole Cutout Dimensions 9 263 156 dia 138 3 2 270 230 60 M5 terminal screws 130 90 20 40 L 230 90 Mounting Hole Cutout Dimensions Four 8 5 dia holes or four M8 screw holes K K M4 terminal sc...

Страница 9: ...2 325 mm2 325 mm2 250 mm2 OTG L82 600 A 82 dia 500 mm2 500 mm2 400 mm2 400 mm2 OTG L156 1 000 A 156 dia 500 mm2 500 mm2 1 000 mm2 1 000 mm2 OTG CN52 200 A 52 dia 200 mm2 200 mm2 150 mm2 100 mm2 OTG CN...

Страница 10: ...as possible or use a shield line When installing a separate type ZCT with current flowing along the primary conductors short the secondary terminals using clips or some other method Switching the Sen...

Страница 11: ...as for calculating ground currents for complete ground faults Depending on the location the allowable ground fault current may be restricted In this case use values of R and C that do not exceed the r...

Страница 12: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syste...

Отзывы: