Functions and Oper
ations
Section 5 Functions and Operations
5-46
5.13 Delaying Output OFF Timing
The output OFF delay function delays the OFF timing for comparative
results.
The shot output (
shot
) is given priority over the OFF delay (
off-d
).
The OFF delay will be disabled if the shot output is set to anything
other than “0,” regardless of the OFF delay setting.
If the measurement value changes and the comparative result that had been ON until now turns OFF, the
comparative output will be held for the time set for the output OFF delay parameter.
The comparative output ON time may be too short if measurement values change quickly. When
comparative output signals are read by external devices, short signals may not be received properly. In
such situations, the output OFF delay can be used to output comparative output signal values for a set
duration or greater.
Output OFF delay is set using the following parameter.
* The unit for K3HB-R settings is 100 ms. For example, if 10 is set,
then the output OFF delay is 10
×
100 ms = 1 s.
Parameter Setting Procedure
Advanced function setting level
R
P
C
Explanation of Functions
Output OFF delay
Parameter
Set value
Meaning of set value
Output OFF delay
off-d
0
to
1999
0 to 1,999 ms (0 to 199.9 s)*
off-d
L
f
(OFF-D)
3 s min.
A
Press the
L
[LEVEL] Key for at least 3 s in RUN level to move to
the initial setting level.
• “
L
0
” is displayed on the level/bank display to indicate the initial
setting level.
B
Press the
M
[MODE] Key several times to change the PV display
to “
amov
.”
• This parameter is not displayed for the initial status due to
setting level protect.
Refer to "5.34 Limiting Key Operations" for information on
removing setting level protect.
C
Press the
S
[SHIFT] Key to make the SV display flash.
• The setting can be changed when the SV display starts to
flash.
D
Use the
U
[UP] and
S
[SHIFT] Keys to set the password “
-
0169
.” Press the
M
[MODE] Key to move to the advanced
function setting level.
• “
L
f
” is displayed on the level/bank display to indicate the
advanced function setting level.
E
Press the
M
[MODE] Key several times to change the PV display
to “
off-d
.”
Displays “L
0
.”
L
0
L
amov
0
L
0
M
amov
00000
L
0
S
init
Displays “L
f
.”
off
L
f
U
M
off-d
0
L
f
M
Содержание K35-2
Страница 2: ......
Страница 24: ...Outline Section 1 Outline 1 8 ...
Страница 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Страница 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Страница 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Страница 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Страница 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Страница 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Страница 185: ......