Functions and Oper
ations
5.9 Averaging Input
5-37
• The data refresh periods when averaging is used are given by
model in the following table.
Averaging is set using the following parameters.
* To not use averaging, set the average type “
avg-t
” to
smpl
and the
averaging times “
avg-n
” to
1
.
Parameter Setting Procedure
Set value
Refresh period
No averaging
1
Every 20 ms
Simple average
2
Every 40 ms
4
Every 80 ms
8
Every 160 ms
16
Every 320 ms
32
Every 640 ms
64
Every 1.28 s
128
Every 2.56 s
256
Every 5.12 s
512
Every 10.24 s
1024
Every 20.48 s
Moving average
1
to
1024
Every 20 ms
Parameter
Set value
Meaning of set value
Averaging type
avg-t
smpl
Simple average
move
Moving average
Averaging times
avg-n
1
1
2
2
4
4
8
8
16
16
32
32
64
64
128
128
256
256
512
512
1024
1024
avg-t
L
1
(AVG-T)
avg-n
L
1
(AVG-N)
3 s min.
A
Press the
L
[LEVEL] Key for at least 3 s in RUN level to move to
the initial setting level.
• “
L
0
” is displayed on the level/bank display to indicate the initial
setting level.
Less
than 1 s
B
Press the
L
[LEVEL] Key once (less than 1 s) to move to the input
adjustment level.
• “
L
1
” is displayed on the level/bank display to indicate the input
adjustment level.
Displays “L
0
.”
L
0
L
avg-t
Displays “L
1
."
smpl
L
1
L
Содержание K35-2
Страница 2: ......
Страница 24: ...Outline Section 1 Outline 1 8 ...
Страница 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Страница 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Страница 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Страница 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Страница 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Страница 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Страница 185: ......