3-18
3-6 Parameter List
3
Operation
Basic Function Mode (F
)
* 2nd control is displayed when SET(08) is allocated to one of the digital inputs.
Extended function mode
Parm
No.
Name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page
F001
Output frequency setting/
monitor
Starting frequency to 1st or 2nd max. frequency
⎯
Yes
Hz
-
4-6
F002
Acceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0
Yes
s
1014 M
1015 L
4-6
F202
*2nd acceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0
Yes
s
1501 M
1502 L
4-6
F003
Deceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0
Yes
s
1016 M
1017 L
4-6
F203
*2nd deceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0
Yes
s
1503 M
1504 L
4-6
F004
Operator rotation direction
selection
00: Forward
01: Reverse
00
No
⎯
1018
4-7
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page
Ba
si
c s
etti
ng
A001
Frequency reference
selection
00: Digital Operator (FREQ adjuster)
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
10: Frequency operation result
00
No
⎯
1019
4-8
A201
*2nd frequency
reference selection
00
No
⎯
-
4-8
A002
RUN command
selection
01: Terminal
02: Digital Operator
03: ModBus communication
02
No
⎯
101A
4-8
A202
*2nd RUN command
selection
02
No
⎯
-
4-8
A003
Base frequency
30. to Max. frequency [A004]
50
No
Hz
101B
4-9
A203
*2nd base frequency
30. to Max. frequency [A204]
50
150C
A004
Maximum frequency
30. to 400.
50
No
Hz
101C
4-10
A204
*2nd maximum
frequency
50
150D
Analog
input
A005
O/OI selection
02: Switches between O/FREQ adjuster via
terminal AT
03: Switches between FI/FREQ adjuster via
terminal AT
04: O input only
05: OI input only
02
No
⎯
101D
4-10
A011
O start frequency
0.0 to Max. frequency
0.0
No
Hz
1020
4-11
A012
O end frequency
0.0 to Max. frequency
0.0
No
Hz
1022
4-11
A013
O start ratio
0. to 100.
0.
No
%
1023
4-11
A014
O end ratio
0. to 100.
100.
No
%
1024
4-11
A015
O start selection
00: External start frequency (A011 set value)
01: 0 Hz
01
No
⎯
1025
4-11
A016
O, OI sampling
1. to 17.
8.
No
⎯
1026
4-12
Содержание JX-A4004
Страница 2: ......
Страница 16: ...14 About This Manual ...
Страница 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Страница 24: ......
Страница 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Страница 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Страница 167: ...Chapter 5 Maintenance Operations 5 1 Special Display List Error Codes 5 2 5 2 Troubleshooting 5 6 ...
Страница 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Страница 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Страница 190: ...7 8 7 3 Dimensional Drawing 7 Specifications JX A2004 AB004 80 5 6 143 1 9 109 5 27 2 6 107 155 67 5 ...
Страница 191: ...7 9 7 3 Dimensional Drawing 7 Specifications JX A2007 80 67 5 5 6 143 1 9 132 5 50 2 6 130 155 ...
Страница 192: ...7 10 7 3 Dimensional Drawing 7 Specifications JX A4004 AB007 110 98 5 5 6 176 189 128 1 9 130 5 28 2 6 ...
Страница 194: ...7 12 7 3 Dimensional Drawing 7 Specifications JX A2055 A2075 A4055 A4075 180 235 165 250 164 6 1 9 167 5 90 1 6 ...
Страница 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Страница 217: ...INDEX ...
Страница 220: ......