3-3
3-1 Test Run Procedure
3
Operation
3-1 Test Run Procedure
•Make sure that the installation conditions are met.
•Select peripheral devices that meet the specifications, and wire correctly.
•Make sure that an appropriate power supply voltage is supplied and that the power input
terminals (R/L1, S/L2, and T/L3) are wired correctly.
JX-A2
: 3-phase 200 to 240 V AC
JX-AB
: 1/3-phase 200 to 240 V AC
(Connect to L1 and N/L3 for 1 phase)
JX-A4
: 3-phase 380 to 480 V AC
•Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the
motor correctly.
•Make sure that the control circuit terminals and the control device are wired correctly
and that all control terminals are turned off.
•Set the motor to no-load status (i.e., not connected to the mechanical system).
•After checking the above, turn on the power.
•When the power is turned on normally, the display shows:
RUN LED indicator
: ON
ALARM LED indicator
: OFF
POWER LED indicator : ON
RUN command LED indicator : ON
Volume LED indicator : ON
Data LED indicator (frequency) : ON
Data display
: Displays the set value in d001.
•If an error occurs, the error code is displayed on the data display. In this case, refer to
"Chapter 5 Maintenance Operations" and make the necessary changes to remedy.
•Set parameter No. b084 to "02", and press the
key while holding down the
and
keys simultaneously.
•Set the motor capacity selection (H003) and the motor pole number selection (H004).
•Use the FREQ adjuster on the Digital Operator to rotate the motor.
•If there is no problem with the no-load operation, connect the mechanical system to the
motor and operate via the Digital Operator.
Item
Description
Reference page
Installation and Mounting
Install the Inverter according to the installation conditions.
2-2
Wiring and Connection
Connect to the power supply and peripheral devices.
2-7
Power On
Check the following before turning on the power.
Display Status Check
Make sure that there are no faults in the Inverter.
Parameter Initialization
Initialize the parameters.
Parameter Settings
Set the parameters required for a test run.
No-load Operation
Start the no-load motor via the Digital Operator.
Actual Load Operation
Connect the mechanical system and operate via the Digital Operator.
Operation
Refer to "Chapter 4 Functions"
, and set the necessary parameters.
Содержание JX-A4004
Страница 2: ......
Страница 16: ...14 About This Manual ...
Страница 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Страница 24: ......
Страница 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Страница 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Страница 167: ...Chapter 5 Maintenance Operations 5 1 Special Display List Error Codes 5 2 5 2 Troubleshooting 5 6 ...
Страница 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Страница 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Страница 190: ...7 8 7 3 Dimensional Drawing 7 Specifications JX A2004 AB004 80 5 6 143 1 9 109 5 27 2 6 107 155 67 5 ...
Страница 191: ...7 9 7 3 Dimensional Drawing 7 Specifications JX A2007 80 67 5 5 6 143 1 9 132 5 50 2 6 130 155 ...
Страница 192: ...7 10 7 3 Dimensional Drawing 7 Specifications JX A4004 AB007 110 98 5 5 6 176 189 128 1 9 130 5 28 2 6 ...
Страница 194: ...7 12 7 3 Dimensional Drawing 7 Specifications JX A2055 A2075 A4055 A4075 180 235 165 250 164 6 1 9 167 5 90 1 6 ...
Страница 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Страница 217: ...INDEX ...
Страница 220: ......