2-22
2-2 Wiring
2
De
sign
Functions and Connections of the Control Circuit Terminals
*1. Simultaneous input of current and voltage is not possible. Do not connect the signal lines simultaneously.
*2. By factory default, multi-function output 11 is set to NO contact. To switch to NC contact, change the C031
setting.
*3. Do not input negative voltage. Doing so may result in damage to the inverter
Terminal
function
Terminal
symbol
Terminal name
Function and connecting method
Wire size
Contact
input
(for
switching
function)
1
2
3
4
5
Multi-function
input
Select functions and allocate them to terminals 1 to 5.
(The figure below illustrates the wiring of the sink logic.)
Shield wire
of 0.14 to
0.75 mm
2
Recomme
nded wire
size:
0.75 mm
2
Power
supply
P24
Internal 24 V DC 24 V DC output
L
Input common
Input signal common
PCS
Input power
supply
If the multi-function input is set as the sink logic, the PCS
terminal acts as an external power supply input terminal.
If the multi-function input terminal is set as the source logic,
the PCS terminal acts as an internal power supply output
terminal.
External
analog
frequency
reference
H
Frequency
reference power
supply output
• External voltage directive is 0 to 9.8 V.
(Nominal input: 10 V)
*1
O
*3
Frequency
reference Input
(Voltage
directive)
OI
*4
Frequency
reference Input
(Current
directive)
L
Frequency
reference
common
Monitor
output
AM
Multi-function
analog output
• Choose from frequency or output current.
Output terminal specifications
0 to 10 V DC full-scale
1 mA max.
Open
Collector
Output
11
Multi-function
output
*2
Output terminal specifications
Between each terminal and PC the
voltage drop is 4V max. at power-on
Open collector output
27 V DC max.
50 mA max.
Select the status of the Inverter and allocate it to terminal 11.
CM2
Multi-function
output common
Relay
output
AL2
AL1
Relay output
Selection of functions is the same as the multi-function
output.
*5 *6
AL0
Relay output
common
L
5
4
3
2
1
H O
OI L
Variable resistor
(1 or 2 W min.)
1 to 2 k
Ω
H O OI L
+
-
0 to 9.8 V DC
(Nominal input: 10 V)
Input impedance 10 k
Ω
H O OI L
-
+
4 to 19.6 mA DC
(Nominal input: 20 mA)
Input impedance 250
Ω
AM
L
CM2
11
RY
Содержание JX-A4004
Страница 2: ......
Страница 16: ...14 About This Manual ...
Страница 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Страница 24: ......
Страница 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Страница 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Страница 167: ...Chapter 5 Maintenance Operations 5 1 Special Display List Error Codes 5 2 5 2 Troubleshooting 5 6 ...
Страница 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Страница 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Страница 190: ...7 8 7 3 Dimensional Drawing 7 Specifications JX A2004 AB004 80 5 6 143 1 9 109 5 27 2 6 107 155 67 5 ...
Страница 191: ...7 9 7 3 Dimensional Drawing 7 Specifications JX A2007 80 67 5 5 6 143 1 9 132 5 50 2 6 130 155 ...
Страница 192: ...7 10 7 3 Dimensional Drawing 7 Specifications JX A4004 AB007 110 98 5 5 6 176 189 128 1 9 130 5 28 2 6 ...
Страница 194: ...7 12 7 3 Dimensional Drawing 7 Specifications JX A2055 A2075 A4055 A4075 180 235 165 250 164 6 1 9 167 5 90 1 6 ...
Страница 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Страница 217: ...INDEX ...
Страница 220: ......