41
Motion Control Modules
Section 2-4
Pulse I/O Specifications
FQM1-MMP21 (Pulse I/O)
Item
Specifications
Pulse
inputs
Number of counters 2
Counter operations
Linear counter and circular counter
Input signals
Two words each for phase A, phase B, and phase Z.
Signal levels
24 V DC, line-driver
Input method
Phase differential
×
1
Phase differential
×
2
Phase differential
×
4
Increment/decrement
Pulse + direction
Counting speed
Voltage
50 k Hz
Line-driver
50 k Hz/500k Hz (phase differen-
tial
×
4, 2 MHz)
Absolute Servo
Driver interfaces
2
SEN output specifications: 5 V PNP output, output
current: 5 mA
When SEN signal is output to Servo Driver, Servo
Driver will transmit the number of encoder's rotations
to this Module. After that, it transmits pulse train cor-
responding to displacement of the number of turns to
the Module.
Pulse
outputs
Number of outputs
2
Output signal
CW/CCW
Signal levels
Line-driver (equivalent to AM26LS31)
Max. output current: 20 mA
Output speed
1 MHz
One-
shot
pulse
outputs
Number of outputs
2
Output type
Open collector (NPN)
Max. switching
capacity
80 mA/5 to 24 V DC
±
10%
Min. switching
capacity
7 mA/5 to 24 VDC
±
10%
Output pulse width
Set time
±
1
µ
s or 0.1% of set time
Содержание HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x TABLE OF CONTENTS...
Страница 11: ...xii...
Страница 23: ...xxiv Data Backup 5...
Страница 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Страница 71: ...48 Memory Block Diagram Section 2 7...
Страница 254: ...231 Analog Outputs Section 7 10...
Страница 255: ...232 Analog Outputs Section 7 10...
Страница 263: ...240 Connecting the CX Programmer Section 8 2...
Страница 285: ...262 Inspections Section 10 1...
Страница 397: ...374 Auxiliary Area Allocations Appendix D...
Страница 409: ...386 Index...
Страница 411: ...388...