B-32
Solid-state Star-delta Timer
H3DS-G
Specifications
■
General
Note:
Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
■
Time Ranges
■
Ratings
Note:
DC ripple rate: 20% max.
Item
H3DS-G
Operating mode
Star-delta operation
Operating/Reset method
Time-limit operation/Self-reset
External connections
Screw terminal, Screw-Less Clamp
Terminal block
Screw terminal type:
Clamps two 2.5-mm
2
max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm
2
max. bar terminals without sleeves.
Terminal screw tightening torque
0.98 N·m max.
Output type
(Star operation circuit) Relay:
SPST-NO
(Delta operation circuit) Relay: SPST-NO
Mounting method
DIN track mounting (see note)
Attachment
Nameplate label
Approved standards
UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 1 A/DC-13; 30 V 0.1 A)
Time scale
Star operation time ranges
x 1
1 to 12 s
x 10
10 to 120 s
Star-delta transfer time
Programmable at 0.05 s, 0.1 s, 0.5 s, or 1 s
Rated supply voltage (see note)
24 to 230 VAC (50/60 Hz)/24 to 48 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-off time: 0.5 s
Reset voltage
2.4 VAC/DC max.
Power consumption
AC: 21 VA max./1.7 W max. (typical: 20 VA/1.6 W) at 230 VAC
11 VA max./2.0 W max. (typical: 8.6 VA/1.5 W) at 100 to 120 VAC
DC: 1.3 W max. (typical: 1.2 W) at 24 VDC
0.7 W max. (typical: 0.6 W) at 48 VDC
Control output
Contact output:
5 A at 250 VAC with resistive load (cos
φ
= 1)
5 A at 30 VDC with resistive load (cos
φ
= 1)
Ambient temperature
Operating: –10
°
C to 55
°
C (with no icing)
Storage:
–25
°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Содержание H3DS Series
Страница 2: ...B 10 Solid state Timer H3DS ...
Страница 14: ...B 22 Solid state Multi functional Timer H3DS M S A ...
Страница 22: ...B 30 Solid state Twin Timer H3DS F ...
Страница 30: ...B 38 Solid state Star delta Timer H3DS G ...