2. Characteristics
G9SX
USER'S GUIDE
77
Ratings and Spec
ifications
Se
ct
io
n
4
2-2 Non-contact Door Switch Controller
Note: 1.
When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2.
Represents the operating time when the safety input turns ON with all other conditions set.
3.
Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set.
4.
The fault detection time for 24-V short-circuit faults on the non-contact door switch input is 35 ms max.
When calculating the safe distance for applications other than as door switches, use a fault detection time of 35 ms.
5.
For the G9SX-
@
-RT (with screw terminals) only.
Item
Model
G9SX-NS202-
@
G9SX-NSA222-T03-
@
Over-voltage category
(IEC/EN 60664-1)
II
Operating time (OFF to ON state)
(See note 1.)
100 ms max. (Logical AND connection input ON
and Non-contact Door Switch input ON)
50 ms max. (Safety input: ON)
(See note 2.)
100 ms max. (Logical AND connection input ON
and Non-contact Door Switch input ON) (See
note 3.)
Response time (ON to OFF state)
(See note 1.)
15 ms max. (Logical AND connection input:
OFF)
20 ms max. (Non-contact Door Switch input OFF)
(See note 4.)
15 ms max. (Safety input OFF and logical AND
connection input OFF)
20 ms max. (Non-contact Door Switch input: OFF)
(See note 4.)
ON-state residual voltage
3.0 V max. (safety output, auxiliary output)
OFF-state leakage current
0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety input,
logical AND connection input, and Non-
contact Door Switch input
100 m max. (External connection impedance: 100
Ω
max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time
---
Within
±
5% of the set value
Insulation
resistance
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
together
20 M
Ω
min. (at 100 VDC)
Between all terminals
connected
together and DIN rail
Dielectric
strength
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
together
500 VAC for 1 min.
Between all terminals
connected together and DIN
rail
Vibration resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction
300 m/s
2
Malfunction
100 m/s
2
Ambient operating temperature
−
10 to 55
°
C (no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque (See note 5.)
0.5 N·m
Weight
Approx. 125 g
Approx. 200 g
Содержание G9SX Series
Страница 50: ...MEMO 50 G9SX USER S GUIDE ...
Страница 95: ...G9SX USER S GUIDE 95 Precautions Precautions ...
Страница 101: ...MEMO G9SX USER S GUIDE 101 ...
Страница 102: ...MEMO 102 G9SX USER S GUIDE ...