78
Services and Addresses
Section 6-4
Note
(1) Specify 1 for a connection with the PLC.
(2) Set ten times the actual value.
0007
Communications Main Set-
ting Number
H’00000000 to H’00000008
0: Automatic assignment
1: CH1 control output (heating) (See note 1.)
2: CH2 control output (heating)
3: CH3 control output (heating)
4: CH4 control output (heating)
5: CH1 control output (cooling)
6: CH2 control output (cooling)
7: CH3 control output (cooling)
8: CH4 control output (cooling)
0008
External Duty Input
Enable/Disable
H’00000000 to H’00000001
0: Disable
1: Enable
0009
Output Mode Selection
H’00000000 to H’00000003
0: Proportional to phase angle (same as G3PX)
1: Proportional to square voltage
2: Proportional to voltage
3: Constant current
000A
Input Digital Filter Time
Constant
H’00000000 to H’000003E8
0.0 to 100 ms (See note 2.)
000B
Input Signal Type
H’00000000 to H’00000001
0: Linear input
1: Voltage ON/OFF input
000C
Main Setting Automatic
Input Selection
H’00000000 to H’00000001
0: 4 to 20 mA or 1 to 5 VDC
1: Communications
000D
Main Setting Manual Input
Selection
H’00000000 to H’00000001
0: External variable resistor input
1: Key input
000E
Control Method Default
H’00000000 to H’00000001
0: Phase control
1: Optimum cycle control
000F
Main Setting Automatic/
Manual Default
H’00000000 to H’00000001
0: Automatic
1: Manual
0010
Number of Alarms for
Heater Burnout Detection
H’00000000 to H’000003E7
0 to 999 alarms
0011
Load Current Upper Limit
H’00000000 to H’00000294
0.0 to 66.0 A (See note 2.)
0: Function disabled.
0012
Event Input Assignment
H’00000000 to H’00000002
0: No assignment
1: Control method selection
2: Main setting automatic/manual selection
0013
Alarm Output Open in
Alarm
H’00000000 to H’00000001
0: Close in alarm (NO contact operation)
1: Open in alarm (NC contact operation)
0014
Heater Burnout Alarm
Operation
H’00000000 to H’00000002
0: Disable
1: Alarm level 1 (fatal error)
2: Alarm level 2 (nonfatal error)
0015
Total Run Time Exceeded
Alarm Operation
H’00000000 to H’00000002
0: Disable
1: Alarm level 1 (fatal error)
2: Alarm level 2 (nonfatal error)
0016
Total Run Time Alarm Set
Value
H’00000000 to H’000003E7
0.0 to 99.9 kh (See note 2.)
0.0: Function disabled
0017
External Input Range
Alarm Operation
H’00000000 to H’00000002
0: Disable
1: Alarm level 1 (fatal error)
2: Alarm level 2 (nonfatal error)
0018
External Duty Input Alarm
Operation
H’00000000 to H’00000002
0: Disable
1: Alarm level 1 (fatal error)
2: Alarm level 2 (nonfatal error)
Address
Data
Data range
Notation
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......