External Contact Input Functions
Section 5-1
5-1
External Contact Input Functions
There are two external contact inputs: the event input (terminals 11 and 12)
and reset input (terminals 13 and 14).
Event Inputs
The event input (terminals 11 and 12) is an external contact input that can be
used for one of the following functions:
• Switching the control method between phase control and optimum cycle
control
• Switching between automatic and manual operation selection
In the initial setting level, set the Event Input Assignment parameter [P11] as
follows to assign one of the above functions to the event input.
When Not Using the Event
Input
Set the parameter to 0 (No assignment). The event input will not function
regardless of its open/closed status.
Note
If a setting other than 0 (No assignment) is selected, the control method and
automatic/manual operation will be switched according to the status of the
event input. If you are not using the event input, always set the parameter to 0:
No assignment.
Selecting the Control
Method with the Event
Input
Set the parameter to 1 (control method selection). The event input can be
used to switch between the following control methods.
• Phase control
• Optimum cycle control
Note
(1) When constant-current control is set as the output mode for phase con-
trol, constant-current control is always used and the control method can-
not be switched by using the event input.
(2) When 1 (control method selection) is set for the Event Input Assignment
parameter [P11], the Control Method Selection (TYP) will not be dis-
played. In addition, if the Control Method Selection parameter is changed
by using communications, an operation error response will be returned.
P11 setting
Meaning
Function of event input
0
No assignment
Does not function as event input.
1
Control method selection
Switches between phase control
and optimum cycle control.
2
Automatic/manual selection
Switches between automatic and
manual operation.
Phase control
Optimum
cycle control
1. RS-485 (+)
2. RS-485 (
−
)
3. Main setting
4. Main setting COM
5. Duty setting
6. Duty setting COM
7. Alarm output 1 (+)
8. Alarm output 1 (
−
)
9. Alarm output 2 (+)
10. Alarm output 2 (
−
)
11. Event input (+)
12. Event input (
−
)
13. Reset input (+)
14. Reset input (
−
)
For standard models, 1 and 2 are not used.
Event input status
Meaning
Open
Phase control
Closed
Optimum cycle control
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......