Setting Parameters in the Initial Setting Level
Section 4-6
4-6
Setting Parameters in the Initial Setting Level
Settings Related to I/O Parameters
Determining the Output Mode
Parameter Setting Procedure
Automatic Input
Setting the Main Setting
Typical Output Mode
•
Automatic operation (4 to 20 mA) based
on the analog current output from a
temperature controller.
•
Automatic operation (1 to 5 V) based on
the voltage output from a temperature
controller.
•
Automatic operation based on a voltage
ON/OFF output from a temperature
controller.
•
Automatic operation based on
communications using the CompoWay/F
protocol for devices such as EJ1 Modular
Temperature Controllers.
Manual Input
•
Main setting set using external variable
resistor
•
Main setting set using keys on front panel
Proportional to phase angle
(same as G3PX)
Proportional to phase angle
(same as G3PX)
ON/OFF control
•
Proportional to phase angle
(same as G3PX)
•
Constant-current control
Proportional to phase angle (same as G3PX)
Proportional to phase angle (same as G3PX)
Output mode
Proportional to
phase angle
(same as G3PX)
Proportional to
square voltage
Proportional
to voltage
Constant-
current control
Optimum cycle
control
ON/OFF control
Parameter
Input Signal Type [P04]
Linear Input
[P04] = 0#
Voltage ON/OFF input
[P04] = 1
Main Setting Automatic/Manual Default
[P08]
Automatic input or
[P08] = 0#
Manual input
[P08] = 1
Automatic input: 4 to 20 mA or 1 to 5 V, or
communications
Manual input: External variable resistor or
key operation
Manual input only
Main Setting Automatic Input Selection
[P05]
Main Setting Manual Input Selection
[P06]
Automatic input
4 to 20 mA or 1 to 5 V, or communications
[P05] = 0# or [P05] = 1
Manual input
External variable resistor or key input
[P06] = 0# or [P06] = 1
Manual input only
External
variable resistor
[P06] = 0#
or
Key
operation
[P06] = 1
Control Method Selection
[P07]
Phase Control
[P07] = 0#
Optimum Cycle
Control
[P07] = 1
Phase Control only
[P07] = *
Output Mode Selection [P02]
Proportional
to Phase
Control (same
as G3PX)
[P02] = 0#
Proportional to
Square Voltage
[P02] = 1
Proportional
to Voltage
[P02] = 2
Constant-
Current Control
[P02] = 3
Optimum Cycle
Control only
[P02] = *
Proportional to
Voltage Control only
[P02] = *
To auxiliary input function setting
#: Default
*: Setting disabled
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......