Soft-start Up and Soft-start Down Functions
Section 5-6
5-6
Soft-start Up and Soft-start Down Functions
The soft-start up and soft-start down functions are used to change the output
value gradually within a set rate of change, even when the input value
changes suddenly. You can set the time for the output value to go from 0% to
100% (i.e., the SUP (soft-start up time)) and the time for the output value to go
from 100% to 0% (i.e., the SDN (soft-start down time)) to a value from 0.0 to
99.9 s.
• Relationships between Input and Output Values and Soft-start Up and
Down Times
!Caution
Specify the soft-start up time so that the inrush current will not be too large. If
the soft-start up time is set too low, the inrush current cannot be suppressed
and the load may be damaged.
Parameter
Setting range (s)
Default (s)
Meaning
Soft-start Up Time
(SUP)
0.0 to 99.9
0.5
The time for the output value
to go from 0% to 100%.
Soft-start Down
Time (SDN)
0.0 to 99.9
0.0
The time for the output value
to go from 100% to 0%.
100
Input value (%)
Output value (%)
Soft-start up time
Soft-start down time
Time
Time
0
100%
0%
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......