90
Error Displays
Section 7-2
Note
To reset the alarm, press the ENT/RST Key or turn ON the RESET input.
Errors for Which the Output Continues (Alarm Level 2)
e60
Total Run Time Thresh-
old Exceeded Alarm
The total run time exceeded the
set value of the Total Run Time
Alarm Set Value parameter.
The internal total run time has exceeded the set
value of the Total Run Time Alarm Set Value param-
eter.
Increase the set value or initialize the total run time.
Use the alarm reset (see note) to clear the error.
e70
Communications Time-
out Alarm
A communications timeout
occurred.
Check whether the communications lines are dis-
connected.
Check whether the host device is operating cor-
rectly.
The error is cleared by correctly writing the main
setting from the host.
Display
Error name
Probable cause
Countermeasures
e40
Heater Burnout Alarm
(when assigned to
alarm level 2)
The heater resistance rate of change
exceeded value set for the Heater Burnout
Threshold (HBR) parameter for more cycles
than the value set for the Number of Alarms
for Heater Burnout Detection parameter
[P09].
Reset the error by using the ENT/RST
Key, execute a reset input from the
RESET terminal, or execute a reset
command via communications.
If more than one error has occurred
consecutively for the output, all of the
errors will be cleared for one reset
operation.
e50
External Input Range
Alarm (when assigned
to alarm level 2)
A 4 to 20-mA or 1 to 5-V input signal was out
of the input range.
e51
External Duty Input
Alarm (when assigned
to alarm level 2)
The external duty variable resistor is discon-
nected.
e60
Total Run Time Alarm
(when assigned to
alarm level 2)
The total run time exceeded the set value for
the Total Run Time Threshold parameter
[P17].
Display
Error name
Probable cause
Countermeasures
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......