![Omron G3PW Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/omron/g3pw/g3pw_user-manual_742699066.webp)
51
Duty Setting
Section 5-3
5-3
Duty Setting
The duty setting function is used to the set rate of change from 0% to 100% of
the output value in relation to the input value (analog input signal, key input
setting, or external variable resistor setting).
There are two duty settings, internal and external. The internal duty setting is
held in the internal memory area and the external duty setting is set by using
an external variable resistor. The duty that is used is the product of the inter-
nal and external duty settings.
Duty value (%) = Internal duty setting (%)
×
External duty setting (%)
Internal Duty Setting
• The internal duty setting is made using either key inputs or communica-
tions (Constant-current Models only).
• The duty setting is held in the internal memory area even when the power
is interrupted.
• The duty is set in the adjustment level (DTY).
External Duty Setting
• The external duty setting is made using an external variable resistor.
• To use the external duty setting function, set the External Duty Input
Enable/Disable parameter [P01] to 1 (enable) in the initial setting level.
Relation between Input
Values and Outputs in
Each Output Mode
1. Control Proportional to Phase Angle (Same as G3PX)
100
40
0 100
50
80
60
20
80%
60%
40%
20%
100%
Output value (%)
Duty setting
Input value (%)
100
40
0 100
60
80
60
20
80%
60%
40%
20%
100%
Output phase angle (%)
Duty setting
Input value (%)
20
40
80
Control Proportional to Phase Angle
(Same as G3PX)
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......