10
Specifications
Section 1-2
Note
1.
When a CS/CJ-series DeviceNet Unit is used as the master, two blocks
can be used for the IN Area (the connections can also be set). When a
CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is used, the
IN Area must be in 1 block, and up to 100 words (200 bytes) are allocated.
(Only polling connections can be used.)
2.
When a CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is
used, up to 32 words can be allocated in the master for a single node.
3.
The set points, alarm setting values, PID constants, and other Tempera-
ture Controller parameters can be set together.
1-2-2
Function and Performance Specifications
Communications distance
Baud rate
Network length
Drop line length
Total drop line
length
500 kbps
100 m max.
(100 m max.)
6 m max.
39 m max.
250 kbps
250 m max.
(100 m max.)
6 m max.
78 m max.
125 kbps
500 m max.
(100 m max.)
6 m max.
156 m max.
The values in parentheses apply when Thin Cables are used.
Communications power supply
11 to 25 VDC
Maximum number of nodes that can be
connected
64 (includes Configurator when used.)
Maximum number of slaves that can be
connected
63
Error control
CRC error detection
Power supply
Power supplied from DeviceNet communications connector (DeviceNet commu-
nications power supply and DeviceNet Communications Unit internal circuit
power supply)
Item
Specifications
Item
Specifications
Maximum number of Temperature
Controllers that can be connected
16
Applicable Temperature Control-
lers
• E5ZN-2QNH03TC-FLK
• E5ZN-2QPH03TC-FLK
• E5ZN-2TNH03TC-FLK
• E5ZN-2TPH03TC-FLK
• E5ZN-2CNF03TC-FLK
• E5ZN-2CPF03TC-FLK
• E5ZN-2QNH03P-FLK
• E5ZN-2QPH03P-FLK
• E5ZN-2TNH03P-FLK
• E5ZN-2TPH03P-FLK
• E5ZN-2CNF03P-FLK
• E5ZN-2CPF03P-FLK
Power supply
Power supplied from Terminal Unit terminal block (terminals 19 and 20) (Communica-
tions power supply between DeviceNet Communications Unit and Temperature Con-
troller, and internal circuit power supply of Temperature Controller)
Copying
The parameters of the connected Temperature Controllers can be uploaded or down-
loaded as a batch, merely by manipulating the DIP switch on the front panel of the
DeviceNet Communications Unit.
The uploaded parameters are stored in the DeviceNet Communications Unit.
Содержание E5ZN-DRT
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi EC Directives 6 ...
Страница 83: ...68 Ladder Programming Examples Section 4 5 ...
Страница 123: ...108 Sending Explicit Messages Section 6 5 ...
Страница 135: ...120 Message Communications Characteristics Section 7 2 ...
Страница 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Страница 159: ...144 Revision History ...
Страница 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...
Страница 162: ...Authorized Distributor Cat No H119 E1 01 Note Specifications subject to change without notice Printed in Japan ...