82
Operations from the Edit Device Parameters Window
Section 5-2
2.
The conduction time monitor and total RUN time monitor cannot be used
at the same time for a single channel.
3.
The total time is not calculated when the communications power to the De-
viceNet Communications Unit is turned OFF.
4.
The DeviceNet Communications Unit checks the ON/RUN status of the
specified Temperature Controller approximately every 0.1 hour (6 min-
utes). Depending on the measurement timing, the accurate may not be ob-
tained due to the timing interval, as shown in the following examples.
Example 1: Using the Unit conduction time monitor when communications power is turned ON and
OFF for three minutes each (A)
In the above diagram, the actual conduction time is 3 minutes
×
3 = 9 minutes,
but the status is ON only once at the time the measurement is taken, so the
conduction time is calculated as 6 minutes.
Example 2: Using the Unit conduction time monitor when communications power is turned ON and
OFF for three minutes each (B)
In the above diagram, the actual conduction time is 3 minutes
×
3 = 9 minutes,
but the status is ON only twice at the time the measurement is taken, so the
conduction time is calculated as 12 minutes.
Example 3: Using the Unit conduction time monitor when communications power is turned ON for 9
minutes, OFF for 3 minutes, and ON for 9 minutes
In the above diagram, the actual conduction time is 9 minutes
×
2 = 18 min-
utes, but the status is ON four times when the measurement is taken, so the
conduction time is calculated as 24 minutes.
ON
OFF
3 min
Calculates ON time
every 6 min approx.
OFF
3 min
ON
Calculates ON time
every 6 min approx.
9 min
OFF
ON
Calculates ON time
every 6 min approx.
Содержание E5ZN-DRT
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi EC Directives 6 ...
Страница 83: ...68 Ladder Programming Examples Section 4 5 ...
Страница 123: ...108 Sending Explicit Messages Section 6 5 ...
Страница 135: ...120 Message Communications Characteristics Section 7 2 ...
Страница 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Страница 159: ...144 Revision History ...
Страница 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...
Страница 162: ...Authorized Distributor Cat No H119 E1 01 Note Specifications subject to change without notice Printed in Japan ...