114
Remote I/O Communications Characteristics
Section 7-1
CS, CJ, C200HX/HG/HE (-Z), and C200HS PLCs
Minimum I/O Response
Time
The minimum I/O response time occurs when the DeviceNet Slave I/O
refreshing is executed just after the input signal is received by the master and
I/O is refreshed for the slave first in the next I/O refresh cycle.
T
IN
:
The Input Slave’s ON (OFF) delay (Minimum value: 0)
T
OUT
:
The Output Slave’s ON (OFF) delay (Minimum value: 0)
T
RT-IN
:
The Input Slave’s communications time/slave
T
RT-OUT
: The Output Slave’s communications time/slave
T
PLC
:
The PLC’s cycle time
T
RF
:
The PLC’s DeviceNet Unit refresh time
Note Refer to the information on each slave for details on Input and Output Slaves’
ON and OFF delay times. Refer to 7-1-2 CompoWay/F Communications
Cycle Time and Refresh Time and the Operation Manual for the PLC being
used for details on the PLC’s cycle time.
The minimum I/O response time (T
MIN
) is the total of the following terms:
T
MIN
= T
IN
+ T
RT-IN
+ (T
PLC
- T
RF
) + T
RT-OUT
+ T
OUT
PLC
T
OUT
T
IN
(T
PLC
−
T
RF
)
T
RT-OUT
T
RT-IN
T
RF
T
PLC
Master Unit
Input
Output
Instruction
execution
Содержание E5ZN-DRT
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi EC Directives 6 ...
Страница 83: ...68 Ladder Programming Examples Section 4 5 ...
Страница 123: ...108 Sending Explicit Messages Section 6 5 ...
Страница 135: ...120 Message Communications Characteristics Section 7 2 ...
Страница 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Страница 159: ...144 Revision History ...
Страница 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...
Страница 162: ...Authorized Distributor Cat No H119 E1 01 Note Specifications subject to change without notice Printed in Japan ...