63
Allocating Data in the Master
Section 4-4
The default connections and connection paths are shown in the following
table.
By setting the following connections as user-defined settings, the IN Area can
be divided into two areas.
Setting from the DeviceNet Configurator
1,2,3...
1.
In the Edit Device Parameters Window for the master, select the Unit in the
General Tab Page, and click the Advanced Setup Button, and then click
the Connection Tab.
Note
If the Auto allocation as is registered item is selected on the mas-
ter’s General Tab Page, a message will be displayed when the con-
nection path is set indicating that the connection has been
changed, causing the current I/O allocations to be cleared. When
setting DeviceNet Communications Unit allocations automatically,
reselect this item after setting a connection.
2.
Select User Setup, and select Use Poll Connection for one connection,
the same as the default setting. Then select the connection path from the
pull-down menu as Out Area 1 for the OUT side, and In Area 1 for the IN
side.
For the second connection, select either Use COS Connection or Use
Cyclic Connection, then select In Area 2 as from the pull-down menu on
the IN side as the connection path. For the connection path on the OUT
side, always set the same connection path as specified for the Poll connec-
tion.
Allocated Area
Connection type used
Connection path used
IN Area 1
Poll
IN Area 1
OUT Area1
Poll
OUT Area 1
IN Area2
None
None
Allocated Area
Connection type used
Connection path used
IN Area 1
Poll
IN Area 1
OUT Area1
Poll
OUT Area 1
IN Area2
COS or Cyclic
IN Area 2
Содержание E5ZN-DRT
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi EC Directives 6 ...
Страница 83: ...68 Ladder Programming Examples Section 4 5 ...
Страница 123: ...108 Sending Explicit Messages Section 6 5 ...
Страница 135: ...120 Message Communications Characteristics Section 7 2 ...
Страница 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Страница 159: ...144 Revision History ...
Страница 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...
Страница 162: ...Authorized Distributor Cat No H119 E1 01 Note Specifications subject to change without notice Printed in Japan ...