102
Examples Using CompoWay/F Commands
Section 6-3
Program Example (Operation 2)
BSET(07 1)
# 0000
D1 020
MO V(021)
# 2801
D1020
MO V(021)
# 0036
D1021
MO V(021)
# 0086
D1022
D1229
MO V(021)
# 0001
D1023
MO V(021)
# 0000
D1024
MO V(021)
# 0001
D1025
A 20011
MOV(021 )
# 01C0
D1 026
MOV(021 )
# 0000
D1 027
MOV(021 )
# 0000
D1 028
MO V(021)
# 0100
D1029
0 00000
Sets 0000 (clears) in D1020 to D1229.
Sets 2801 in D1020. (Command code = 28 01)
Sets 0086 in D1022. (Class ID = 86)
Sets 0001 in D1023. (Instance ID = 01)
Sets 0001 in D1025. (SID = 00, MRC = 01)
Sets 0000 in D1027. (Read address = 0000)
Sets 0100 in D1029. (Number of elements = 01)
First Scan
Flag ON
Sets 0036 in D1021.
(Slave node address = 00, service code = 36)
Sets 0000 in D1024.
(E5ZN Unit No. = 00, sub-address = 00)
Sets 01C0 in D1026.
(SRC = 01, variable type = C0)
Sets 0000 in D1028
(Bit position = 00, No. of elements = 00)
Содержание E5ZN-DRT
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi EC Directives 6 ...
Страница 83: ...68 Ladder Programming Examples Section 4 5 ...
Страница 123: ...108 Sending Explicit Messages Section 6 5 ...
Страница 135: ...120 Message Communications Characteristics Section 7 2 ...
Страница 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Страница 159: ...144 Revision History ...
Страница 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...
Страница 162: ...Authorized Distributor Cat No H119 E1 01 Note Specifications subject to change without notice Printed in Japan ...