72
Wiring and Connections
Section 3-4
PC Setup Settings
The input bits shown in the following tables can operate as normal inputs or
they can be assigned special functions in the PC Setup.
Special functions for input bits IR 00000 through IR 00002 are set in
DM 6642:
Special functions for input bits IR 00003 through IR 00006 are set in
DM 6628:
High-speed Counter Input Connection Examples
Bit
address
PC Setup setting (DM 6642 bits 08 to15)
00
01
02, 03, or 04
IR 00000
Used as normal
inputs.
Used as high-speed
counter inputs.
Used as inputs for synchro-
nized pulse control.
IR 00001
IR 00002
Used as a normal input.
Bit
address
Bits in
DM 6628
PC Setup setting (in DM 6628)
0 (Hex)
1 (Hex)
2 (Hex)
IR 00003
00 to 03
Used as normal
inputs.
Used as interrupt
inputs (including
counter mode).
Used as quick-
response inputs.
IR 00004
04 to 07
Differential Phase Mode
(Count frequency: 5 kHz)
E6B2-CWZ6C
Encoder
(NPN open-col-
lector output)
24 VDC
00000 A-phase input
00001 B-phase input
COM
00002 Z-phase input
Pulse Plus Direction Input mode
(Count frequency: 20 kHz)
E6A2-CS5C
Encoder
24 VDC
00000 Pulse input
00001 Direction input
COM
00002 Reset input
Sensor or
switch
Sensor or
switch
Sensor
power
Black
White
Orange
Brown
Blue
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......