109
Basic PC Operation and I/O Processes
Section 4-7
Input Time Constants for IR 000
Input Time Constants for IR 001 to IR 009
The nine possible settings for the input time constant are shown below. (Set
only the rightmost digit for each setting for IR 000.)
00 (Hex): 8 ms 01 (Hex): 1 ms 02 (Hex): 2 ms
03 (Hex): 4 ms 04 (Hex): 8 ms 05 (Hex): 16 ms
06 (Hex): 32 ms 07 (Hex): 64 ms08 (Hex): 128 ms
4-7-9
Error Log Settings
Error Detection and Error Log Operation (DM 6655)
Make the settings shown below to determine whether or not a non-fatal error
is to be generated when the cycle time exceeds 100 ms or when the voltage
of the built-in battery drops, and to set the method for storing records in the
error log when errors occur.
Battery errors and cycle time overrun errors are non-fatal errors.
Refer to
below for details on the error log.
15
0
Bit
Not used.
Time constant for IR 00005 (1 digit BCD; see below.)
Time constant for IR 00003 to IR 00004 (1 digit BCD; see below.)
Time constant for IR 00000 to IR 00002 (1 digit BCD; see below.)
Default:
0000 (8 ms for each)
DM 6620
15
0
Bit
DM 6621: IR 001 and IR 002
DM 6622: IR 003 and IR 004
DM 6623: IR 005 and IR 006
DM 6624: IR 007 and IR 008
DM 6625: IR 009
Time constant for IR 002, IR 004, IR 006, and IR 008
Time constant for IR 001, IR 003, IR 005, IR 007, and IR 009
Default:
0000 (8 ms for each)
DM 6621 to DM 6625
Low battery voltage detection
0 (Hex): Detect
1 (Hex): Don't detect
15
0
DM6655
0
Bit
Always
0
Cycle time over detection
0 (Hex): Detect
1 (Hex): Don't detect
Error log storage method
0 (Hex): Error records for the 7 most recent errors always stored (older errors de-
leted).
1 (Hex): Only the first 7 error records stored (no errors stored beyond that point).
2 to F (Hex): Error records not stored.
Default:
Low battery voltage and cycle time over errors detected, and error records
stored for the 7 most recent errors.
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......