128
Explicit Message Communications
Section 6-3
ERROR RESPONSE
The CPM2C-S returns an error response when there is an error in the explicit
message command sent from the DeviceNet Master.
Response Format
Parameters
Number of bytes received (response)
Indicates the number of bytes of data (in hexadecimal) from the “source node
number.”
Source node number (response)
Indicates the node number (in hexadecimal) of the CPM2C-S that returned
the response.
General error code (response)
Indicates the nature of the error with one of the 1-byte (2-digit hexadecimal)
error codes listed in the following table.
Additional error code (response)
Always FF (Hex).
6-3-3
Examples of DeviceNet Explicit Messages
CS/CJ, CVM1, and CV-series PCs: Reading Data with CMND(194)
This example shows the instruction operands and results when 20 words of
data (IR 010 to IR029) in a Slave are read through a Master mounted in a CS/
CJ, CVM1 or CV-series PC.
For details on explicit messages, refer to the
CS/CJ Series DeviceNet Units
Operation Manual
(W380) for CS/CJ-series PCs, and refer to the
DeviceNet
Operation Manual
(W267) for CVM1 and CV-series PCs. For details on
CMND(194), refer to the
CS Series Programmable Controllers Operation
Manual
(W339) for CS-series PCs, and refer to the
CVM1/CV Series CV500/
CV1000/CV2000/CVM1 Programmable Controllers Operation Manual: Ladder
Diagrams
(W202) for CVM1 and CV-series PCs.
Example Network
Conditions
Master’s node number:
63
Slave’s network address: 1
Slave’s node number:
2
Code
Error name
Meaning
08 (Hex)
Service not supported
The service code was invalid.
15 (Hex)
Too much data
There was too much data. (For example, the
amount of write data exceeded the data area
boundary.)
13 (Hex)
Not enough data
There was too little data. (For example, an odd
number of bytes of write data were used in a
WRITE WORD DATA command.)
20 (Hex)
Invalid parameter
The starting word address was invalid.
11 (Hex)
Reply data too large
The data area boundary was exceeded in a
DATA READ command.
16 (Hex)
Object does not exist
The class ID or instance ID was invalid.
Number of bytes received
Source node number
General error code
Additional error code
(Always FF)
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......