202
Initial System Checks and Test Run Procedure
Section 9-1
9-1
Initial System Checks and Test Run Procedure
9-1-1
Initial System Checks
Check the following items after setting up and wiring the CPM2C-S, but before
performing a test run.
Note
1.
Always clear memory before beginning to program the CPM2C-S. Al-
though memory is cleared before the CPU Unit is shipped, the contents of
the DM, HR, AR, and counter areas may change in transit. See
for details on the All Clear operation.
2.
See
1-3-3 Operating Mode at Startup
CPM2C-S will enter when the power is turned ON.
9-1-2
Flash Memory Precautions
Observe the following precautions to protect the flash memory and ensure
proper operation.
1,2,3...
1.
If changes are made in the read-only DM area (DM 6144 through DM
6599) or PC Setup (DM 6600 through DM 6655), the PC’s operating mode
must be changed to write the new contents to flash memory. If backup bat-
tery is changed before the changes are written to flash memory, the chang-
es will be lost.
The changes can be saved by switching the CPM2C-S to RUN or MONI-
TOR mode or turning the CPM2C-S OFF and then ON again.
2.
When contents of the program, read-only DM (DM 6144 through DM
6599), or PC Setup (DM 6600 through DM 6655) have been changed, star-
tup processing will take up to 1,200 ms longer than usual. Be sure to take
this one-time startup delay into account if it may affect operations.
3.
If one of the following three operations is performed in MONITOR or RUN
mode, the CPM2C-S’ cycle time will be extended by up to 1,200 ms and
interrupts will be disabled while the program or PC Setup is being overwrit-
ten.
• Program changes with the online edit operation
• Changes to the read-only DM area (DM 6144 through DM 6599)
• Changes to the PC Setup (DM 6600 through DM 6655)
A “SCAN TIME OVER” error won’t occur during these operations. Be sure
to take this delay in the CPM2C-S’ I/O response times into account when
performing online editing.
9-1-3
CPM2C-S Test Run Procedure
1,2,3...
1.
Power Supply Application
a) Check the CPM2C-S’ power supply voltage and terminal connections.
b) Check the I/O devices’ power supply voltage and terminal connec-
tions.
c)
Turn ON the power supply and check that the “PWR” indicator lights.
Item
Points to check
Power supply and I/
O connections
Is the wiring correct?
Are the terminals securely tightened?
Are there any shorts between crimp terminals or wires?
Refer to
for details.
Connecting cables
Are the cables all connected correctly and locked?
Refer to
for details.
Protective label
Has the protective label been removed?
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......