91
I/O Allocation to CompoBus/S Slaves
Section 4-3
4-3
I/O Allocation to CompoBus/S Slaves
The CompoBus/S input area (IR 020 to IR 027) and CompoBus/S output area
(IR 030 to IR 037) are allocated for the CompoBus/S Terminal’s I/O. The fol-
lowing table shows the I/O allocation of the CompoBus/S Terminal (IN0 to
IN15 and OUT0 to OUT15.)
Note
1.
IN0 to IN15 are node numbers of Input Terminals and OUT0 to OUT15 are
node numbers of Output Terminals.
2.
When the maximum number of CompoBus/S nodes is set to 16, IN8 to
IN15 and OUT8 to OUT15 can be used as work bits.
3.
CompoBus/S Terminals with 8 points or less are allocated I/O bits in byte
units beginning from bit 00 or bit 08.
4.
Only even addresses can be specified for 16-point CompoBus/S Termi-
nals.
I/O
Bit address
IR word
Bit number
15 14 13
12
11 10
9
8
7 6 5 4 3 2 1 0
Input area
020
IN1
IN0
021
IN3
IN2
022
IN5
IN4
023
IN7
IN6
024
IN9
IN8
025
IN11
IN10
026
IN13
IN12
027
IN15
IN14
Output area
030
OUT1
OUT0
031
OUT3
OUT2
032
OUT5
OUT4
033
OUT7
OUT6
034
OUT9
OUT8
035
OUT11
OUT10
036
OUT13
OUT12
037
OUT15
OUT14
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......