50
Sect
ion 3
CompoN
et
Communic
a
tions
Spec
if
ic
at
ions
E3NW-CRT
User’s Manual
Section 3
Explicit Message Communications
Service Code
When the command is completed normally, the leftmost bit of the service code that is
specified in the command is turned ON and the service code is stored as follows:
When an error message is returned for an explicit message, the returned service code
will always be 94 hex.
Data: The read data is stored only when a read command has been sent.
Error Code: The error code for the explicit message.
Refer to Error Codes on page 59.
• With this Sensor Communications Unit, some commands (such as power tuning commands)
require time to be processed. Change the timer set value for these commands. Set the
CompoNet message monitoring timer to 30 seconds or longer.
Refer to 6-1-5 Message Monitoring Timer in the CS1W-CRM21/CJ1W-CRM21 CompoNet
Master Units Operation Manual (Cat. No. W456).
Command service code
Response service code
10 hex
90 hex
0E hex
8E hex
16 hex
96 hex
06 hex
86 hex
07 hex
87 hex
05 hex
85 hex